CV3100 series and MINI series high performance general purpose inverter instruction manual
9-6
Sizes
00H
01H
CRC CHK Low
64H
CRC CHK High
0BH
Response massage frame format:
Address
01H
Function
03H
data byte number
02H
Data content
10H
88H
CRC CHK Low
B5H
CRC CHK High
E2H
Query the frame
:
01H+03H+00H+06H+00H+01H+64H+0BH
Specific meaning is as follows:
Address
:
01H ---- this device ID is 01H
Function
:
03H ---- read register function code
Starting data address
:
0006H ----register address is 0x0006
,
indicates
read parameters from this register.
Sizes
:
0001H ----readout one register data
CRC CHK
:
Reference to the last page for methods to get RTU mode check
code (CRC Check).
Response the frame
:
01H+03H+02H+10H+88H+B5H+E2H
Specific meaning is as follows:
Address
:
01H ----This device ID is 01H
。
Function
:
03H ---- read out register function code
data byte number:02H ----Indicates read the content length for 2 registers
Data content
:
1088H----Indicates readout content
CRC CHK
:
Reference to the last page for methods to get RTU mode check