CV3100 series and MINI series high performance general purpose inverter instruction manual
6-48
P6.13
Sleeping threshold
Factory setting
10.00V
Setting range
0.0—10.00V
This parameter defines inverter feedback limit from working status to sleeping status.
If the feedback value is more than the setting value, when the inverter output
frequency drops to low limit frequency after the delay time of P6.15,then the
inverter go into sleeping.(0 rotate speed running)
P6.14
Waking threshold
Factory setting
0.00V
Setting range
0.0—10.00V
P6.15
Sleep/Wake waiting time
Factory setting
300.0S
Setting range
0.1—600.0S
P6.14 parameter defines inverter feedback limit from sleeping status to working
status,P6.15 parameter defines the transferring time between sleep and wake status. If
the feedback value is less than the setting value, the inverter will wake up from
sleeping status after P6.15 waiting delay time and start to run again.
Sleeping threshold
Waking threshold
PID setting
Output frequency
Lower limit
frequency
PID feedback
sleeping
waking
P6.15
P6.15
Diagram 6-25 Sleeping & waking function