HCM-IMM (10/16)                                                                                                                  7 

 

Location Requirements for the Hybrid Cooling Module: 

1.  Within 20 feet of the earth loop line set. Minimize refrigerant line lengths. 

2.  No more than 20 feet higher than the earth loop manifolds. 

3.  With proper clearances around the unit: 

  24 inches minimum on the two sides and back (coil side) 

  36 inches minimum on the front (fan side) 

4.  Away from windows, patios, decks, etc., where unit operation sounds may disturb the 

occupants. 

5.  On a solid, level mounting pad. The mounting pad should extend a minimum of 2 inches 

beyond the cabinet size of the Hybrid Cooling Module.  

The minimum pad size is to be 

16 inches by 40 inches. 

 The pad should NOT be in contact with or be an integral part 

of the building foundation.  The following DiversiTech Pads (or their equivalent) are 
recomm

ended.  The standard pads are 2” thick.  Local building codes may require a 3” 

thick pad. 

Model Number 

Size, Inches 

Comments 

Ultralite

®

 UC2448-2 

24 x 48 x 2 

Fiber-cement construction 

Ultralite

®

 UC2448-3 

24 x 48 x 3 

Fiber-cement construction 

Elite

®

 EL3648-2 

36 x 48 x 2 

Plastic-drillable for securing unit 

Elite

®

 EL3648-3 

36 x 48 x 3 

Plastic-drillable for securing unit 

 

6.  Where conditions or local codes require the Hybrid Cooling Module to be attached to a 

mounting pad or frame, tie down bolts should be used to fasten through the holes 
provided in the Hybrid Cooling Module feet. 

7.  Elevate the Hybrid Cooling Module per local climate and code requirements to provide 

clearance above estimated snowfall level and ensure adequate water drainage of Hybrid 
Cooling Module. Use snow stand in areas where prolonged freezing temperatures are 
encountered. 

 

Do NOT Locate the Hybrid Cooling Module: 

1. 

On brick, concrete blocks or unstable surfaces 

2. 

Near clothes dryer exhaust vents 

3. 

Near sleeping area or near windows 

4. 

Under eaves where water, snow or ice can fall directly in the unit 

5. 

Within clearance less than 2 feet from a second unit 

6.  Within the minimum distance the Hybrid Cooling Module can be installed from the 

property line, where local zoning ordinances apply. 

 

Summary of Contents for HCM-1860C

Page 1: ...HCM IMM 10 16 2016 EarthLinked Technologies Inc HybridCoolingModule Model HCM 1860C R410A Installation and Maintenance Manual...

Page 2: ...l Failure to provide installation by an ETI trained and authorized technician in a manner consistent with this manual will void and nullify the limited warranty coverage for the system EarthLinked Tec...

Page 3: ...Placement 6 Installation Refrigerant Connections 8 Installation Electrical Start Up 10 Maintenance Regular Care 13 LIST OF REVISIONS New Hybrid Cooling Module New condensing temperature controller On...

Page 4: ...rthLinked systems will require the use of two 2 field supplied Type ACR copper couplings to match the HCM with the line set vapor tube size See the table below to determine the required coupling sizes...

Page 5: ...ons and Data WARNING Inhalation of high concentrations of refrigerant gas vapor is harmful and may cause heart irregularities unconsciousness or death Vapor reduces oxygen available for breathing and...

Page 6: ...refrigerant and water lines between these above ground components must be insulated with at least 1 2 wall thickness Armaflex Insul Tube or equivalent insulation Thicker insulation is recommended for...

Page 7: ...x 48 x 2 Fiber cement construction Ultralite UC2448 3 24 x 48 x 3 Fiber cement construction Elite EL3648 2 36 x 48 x 2 Plastic drillable for securing unit Elite EL3648 3 36 x 48 x 3 Plastic drillable...

Page 8: ...r a trench 3 to 4 feet deep is to be excavated running from the Hybrid Cooling Module to the earth loop line set If the lines to and from the Hybrid Cooling Module are to be run parallel to and within...

Page 9: ...the Hybrid Cooling Module line sets and earth loop system are to be brazed with 15 silver content brazing alloy utilizing the NITROGEN BRAZING PROCESS CAUTION NITROGEN BRAZING PROCESS PURPOSE Utilize...

Page 10: ...ACCESS PANELS AND INITIATING ANY PHASE OF THIS INSTALLATION MAKE SURE THAT POWER IS TURNED OFF TO ALL EARTHLINKED AND FIELD SUPPLIED SYSTEM COMPONENTS FAILURE TO DO SO COULD RESULT IN PROPERTY DAMAGE...

Page 11: ...HCM IMM 10 16 11 Figure 5 Hybrid Cooling Module Field Wiring Figure 6 Hybrid Cooling Module Field Wiring Seal tight Line voltage entrance...

Page 12: ...ure 7 Figure 7 Hybrid Cooling Module Sensor Wiring 4 The Hybrid Cooling Module contains a thermostatic actuated fan speed control that has been factory set for a pre determined R 410A system condensin...

Page 13: ...arthLinked support at 1 863 701 0096 for help Regular Care Keep the Hybrid Cooling Module free of foliage grass clippings leaves paper and any other material that could restrict the proper air flow in...

Reviews: