Pre-Installation 

 

 

 

This Hybrid Cooling Module (HCM) is pre-programed using A-419 temperature controllers. A 
sensor connector is pre-installed in the HCM cabinet and the sensor is to be placed on the liquid 
line. This allows for temperature-based fan control: the HCM cycles on when the liquid line 
temperature reaches 110

F and cycle off once when the liquid line temperature drops to 105

F. 

This temperature range is high enough to keep the Cooling Assist Valve closed and low enough 
to keep the head pressure down when needed.

 

If the HCM is installed as a retrofit, the refrigerant charge in the existing system must be 
recovered before HCM installation. Use new refrigerant to recharge the system. 

Application of the Hybrid Cooling Module (HCM) to EarthLinked

®

 systems will require the 

use of two (2) field supplied Type ACR copper couplings to match the HCM with the line 
set vapor tube size.  

See the table below to determine the required coupling sizes. 

 

COMPRESSOR UNIT/HCM MODEL MATCH 

Compressor 

Unit Model 

Hybrid Cooling Module 

Vapor Line Set Size, 

OD, in. 

Model HCM  

Connections 

OD, In. 

R-410A 

018 to 060 

-1860C 

7/8 

7/8 

 

 

 

 

 

IMPORTANT! 

This EarthLinked® Hybrid Cooling Module (HCM) is for use with EarthLinked® 
space heating and cooling systems that provide cooling. The HCM is a required 
component of the EarthLinked® systems where indicated in the EarthLinked® 
Performance Tables for R-410A systems. 

WARNING! 

Before installing this Hybrid Cooling Module (HCM), be sure that all 
electrical power to the EarthLinked® system is “OFF”. Wear adequate 
protective clothing and practice all applicable safety precautions 
when installing this equipment. Failure to do so may result in 
equipment and/or property damage, personal injury or death.

 

Summary of Contents for HCM-1860C

Page 1: ...HCM IMM 10 16 2016 EarthLinked Technologies Inc HybridCoolingModule Model HCM 1860C R410A Installation and Maintenance Manual...

Page 2: ...l Failure to provide installation by an ETI trained and authorized technician in a manner consistent with this manual will void and nullify the limited warranty coverage for the system EarthLinked Tec...

Page 3: ...Placement 6 Installation Refrigerant Connections 8 Installation Electrical Start Up 10 Maintenance Regular Care 13 LIST OF REVISIONS New Hybrid Cooling Module New condensing temperature controller On...

Page 4: ...rthLinked systems will require the use of two 2 field supplied Type ACR copper couplings to match the HCM with the line set vapor tube size See the table below to determine the required coupling sizes...

Page 5: ...ons and Data WARNING Inhalation of high concentrations of refrigerant gas vapor is harmful and may cause heart irregularities unconsciousness or death Vapor reduces oxygen available for breathing and...

Page 6: ...refrigerant and water lines between these above ground components must be insulated with at least 1 2 wall thickness Armaflex Insul Tube or equivalent insulation Thicker insulation is recommended for...

Page 7: ...x 48 x 2 Fiber cement construction Ultralite UC2448 3 24 x 48 x 3 Fiber cement construction Elite EL3648 2 36 x 48 x 2 Plastic drillable for securing unit Elite EL3648 3 36 x 48 x 3 Plastic drillable...

Page 8: ...r a trench 3 to 4 feet deep is to be excavated running from the Hybrid Cooling Module to the earth loop line set If the lines to and from the Hybrid Cooling Module are to be run parallel to and within...

Page 9: ...the Hybrid Cooling Module line sets and earth loop system are to be brazed with 15 silver content brazing alloy utilizing the NITROGEN BRAZING PROCESS CAUTION NITROGEN BRAZING PROCESS PURPOSE Utilize...

Page 10: ...ACCESS PANELS AND INITIATING ANY PHASE OF THIS INSTALLATION MAKE SURE THAT POWER IS TURNED OFF TO ALL EARTHLINKED AND FIELD SUPPLIED SYSTEM COMPONENTS FAILURE TO DO SO COULD RESULT IN PROPERTY DAMAGE...

Page 11: ...HCM IMM 10 16 11 Figure 5 Hybrid Cooling Module Field Wiring Figure 6 Hybrid Cooling Module Field Wiring Seal tight Line voltage entrance...

Page 12: ...ure 7 Figure 7 Hybrid Cooling Module Sensor Wiring 4 The Hybrid Cooling Module contains a thermostatic actuated fan speed control that has been factory set for a pre determined R 410A system condensin...

Page 13: ...arthLinked support at 1 863 701 0096 for help Regular Care Keep the Hybrid Cooling Module free of foliage grass clippings leaves paper and any other material that could restrict the proper air flow in...

Reviews: