Mounting/Location
The Desuperheater is mounted vertically on a solid surface indoors in a space with ambient
temperatures of 40°F or above. The Desuperheater is to be located within 10 feet of the
compressor unit and as close as possible to the storage water heater (not to exceed 25 feet),
with interconnecting water lines insulated.
Controls
As illustrated in Figures 3a and 3b, the Desuperheater contains a water high limit control. It is
factory set to 140°F. It also contains a refrigerant gas low limit, which is factory set to 125°F.
The freeze protection control is designed to operate the circulating pump when water
temperatures of 40°F or less are detected, in order to provide water circulation independent of
compressor operation.
Heat Exchanger
The Model DSH-1872 Desuperheater contains a corrosion resistant all-copper double wall heat
exchanger of counterflow twin tube design. The heat exchanger is continuously vented along its
entire length and meets IAPMO safety requirements and exceeds applicable UL requirements.
Circulator Pump
The Desuperheater contains a Taco 006 series low wattage wet rotor in-line single stage
circulator. The water cooled pump is rated at 60 watts, 230 volts and 0.40 amperes. It is
designed for 125 psig working pressure and up to 220°F fluid temperature. The pump housing is
bronze and the bearings are ceramic.
Summary of Contents for DSH-1872
Page 5: ...DSH KIT 04 13 Page 5 Figure 2 Desuperheater installed with GSTE Storage Water Heater...
Page 6: ...DSH KIT 04 13 Page 6 Figure 3a SC Field Wiring for Desuperheater Kit...
Page 7: ...DSH KIT 04 13 Page 7 Figure 3b CC Compressor Unit Field Wiring...
Page 11: ...DSH KIT 04 13 Page 11 Figure 4 SC Cabinet Dimensions and Connections...
Page 12: ...DSH KIT 04 13 Page 12 Figure 5 CC Cabinet Dimensions and Connections...
Page 13: ...DSH KIT 04 13 Page 13 Figure 6 SC Internal Flow Schematic with Desuperheater...
Page 14: ...DSH KIT 04 13 Page 14 Figure 7 SC Piping with Desuperheater...
Page 15: ...DSH KIT 04 13 Page 15 Figure 8 CC Internal Flow Schematic with Desuperheater...
Page 16: ...DSH KIT 04 13 Page 16 Figure 9 CC Piping with Desuperheater...