38
SLB-Series User Manual
Zero calib
Z0=5.0
Z1=0.0
Z2=400.0 Z3=400.0
calibrating...
Zero Calibration
After the zero calibration is complete the values should be as follows:
Z0:
Between 5 and 25
Z1:
0.0
Z2:
Between 400 and 600
Z3:
Between 400 and 600
Measurement Calibration
This function is used to calibrate voltage and current values. (
Password: 9577
) For a string
voltage calibration, an accurate multi-meter is needed.
Select
[Measure calib]
under the
[Param manage]
menu to select a calibration method.
Measure calib
Strg U calib
DIS I calib
Save param
Calibration Menu
To perform a String Calibration:
1.
Select
[String U calib]
2. Connect the string voltage test leads to the poles of the battery string
3. Select the nominal voltage of the string, this value should be identical to the nominal
voltage of the load bank
Select String Voltage
Select V type
Strg type:
48V
Cancel
Confirm
www.
GlobalTestSupply
.com