32
SLB-Series User Manual
1. Set the parameters for the first string,
“String No.”
indicates current string
2. Change
“String No.”
from
“1”
to
“2”
and so on to change parameters for each string
3. Press the
down
arrow to set parameters for the parallel strings
4. Press
ENT
to start the test.
Continued Discharge
It is possible to continue a discharge test that has stopped for various reasons such as cutoff
values met or manual stop. To continue a stopped discharge:
1.
Enter the menu and select
[Battery DIS]
then select
[Continued DIS]
2. If the test was stopped due to cells with low voltage, then a maximum of 6 cells can be
ignored so that the test can continue.
NOTE:
Ignored cells will still be discharged unless
removed from the string. It is recommended to adjust the overall system voltage cut-off
to reflect the number of cells removed.
3. Press
ENT
to start the continued discharge.
Ignore Cells with Low Voltage
Parallel Load Test
If the required discharge current is higher than the rated value of the load bank another
SLB-Series load bank of the
same nominal voltage
can be used in parallel to increase the
discharge current.
NOTE:
Only units with the same nominal voltage rating can be used in
parallel
. For example, a 48V 100A and a 48V 200A load bank can be used in parallel to
discharge up to 48V 300A.