3.4 Power Up
WARNING
Each time the unit is turned on it performs a self-test, which activates visual alarms. If
the self-test fails, or if all the alarms do not activate, do not use. Failure to do so may
adversely affect product performance and result in sickness or death.
The Eagle Eye GD-3000 Combustible Gas Detector cycles through an internal self-test
cycle for the first minute that it is powered. The unit will execute the test cycle any time
power is dropped and reapplied (i.e. power failure). During the self-test cycle the unit
will display the firmware version number, then count down from 60 to 0 and finally go
into normal operation. The fan and alarm relay will be activated for the power-up cycle
unless the “Power Up Test” (PUt) option is OFF. The indicator light (LED) will flash
green during the self-test cycle. At the end of the 1 minute cycle, the unit will take its
first sample of the air and the light will turn solid green.
WARNING
Do not cover or obstruct visual alarm LED. Doing so may adversely affect product
performance and
result in sickness or death
.