background image

These installation instructions provide essential information for installing VESDA ECO gas detector in accordance with the system design. Additional installation and product 
documentation is listed below in the Reference Documents section.

VESDA ECO Installation Instructions

System Components

As shipped, the product packaging contains the following items which are required for 
installation and commissioning of the product:

• 

VESDA ECO Gas Detector

• 

VESDA ECO Product Guide

• 

USB Interface Lead

•  MicroSD Card (supplied fitted into card slot)

• 

Test and Calibration Equipment as per Test Gas Guide 19517

•  ¼ in or 6mm flex tubing to adapt to test gas regulator

Prerequisites

• 

A completed system design.

• 

A 24V DC Power Supply and backup battery, compliant with local codes and 
standards.

•  Standard mini-B USB cable, required for initial configuration of the detector.

•  Conduit, as specified in the system design.

• 

1.5 mm

(16 AWG).

• 

0.2 mm

2

 to 1.5 mm

2

 (24 - 16 AWG) wiring for relays.

•  A PC or laptop installed with Xtralis VSC for initial configuration.

• 

Standard connection instructions for where the detectors are to be added to a corporate 
network.

Power Consumption

3.6W @ 24 V DC for dual gas detector

Environmental Requirements

• 

Temperature

 

• 

Ambient:

 -20 to 55ºC (-4 to 131ºF) gas dependent

• 

Sampled Air:

 -20 to 55ºC (-4 to 131ºF)

• 

Humidity:

  10-95% RH, non-condensing

Note: 

 

Please consult your Xtralis representative for information on operation outside 
these parameters.

Reference Documents

Additional installation and product information is contained in the following document, 

which is available for download in the Xtralis partner extranet at www.xtralis.com.
• 

17898 - VESDA ECO Detector Product Guide

Installation Process

To obtain the benefit of peak performance from the ECO product, it is suggested that you 

follow the recommended installation procedure as outlined below:

•  Detector Location: Determine the optimum position to place the ECO to maximize its 

ability to detect the gas hazard.

• 

Physical Installation: Mount the ECO correctly in its selected location.

• 

Electrical Installation: Connect the power and other interface wiring.

•  Setup Xtralis VSC: Install the free Xtralis VSC configuration software and connect 

the PC to ECO USB port. Read and modify the factory default settings, review and 
download event logs.

• 

Set Date and Time: Set the ECO system date and time to ensure logged events are 
correctly time stamped.

•  Flow Normalization: Normalize the air flow reading to provide the reference for the flow 

fault conditions.

•  Gas Sensor Check: Bump test the product using a calibrated sample gas to confirm 

proper measurement operation of the gas sensors.

• 

System Test: Use the Gas Test function in Xtralis VSC to verify the operation of the 
alarms, relays and current outputs.

• 

Installation Checklist: Complete and retain the installation checklist.

Air Inlet/Outlet Pipe Connections

The tapered shape of the air inlet/outlet port of the ECO is designed to accept standard 

pipes of OD 25mm (ID 21 mm) or BSP ¾ in (OD 1.05 in) and as such provide an air tight 

seal without gluing. Connection to pipe networks of other sizes should not be done without 

first confirming their compatibility with your Xtralis representative.

Flow Shutoff

Due to the effects of pressure variations across an installation it is recommended that 
a suitable shutoff valve is installed immediately before the ECO in the pipe work, i.e. 
on the sample inlet side. This will help to prevent ambient pressure differentials caused 

by aggressive air conditioning from generating sample flow through the ECO during 

calibration when the aspirator is shut off. 

During calibration or bump testing no air flow should pass through the ECO detector. The 

shut off isolation valve will provide a simple means of accomplishing this.

Notes: 

 

Do not install your ECO detector if there are any signs of shipping damage. 
Inform your distributor if there is any visible damage.

 

Check that the model of the ECO detector is correct as per the design 

specifications of the site. Refer to the model number located on the main 

product label and ensure that the gas types and ranges are of the correct 

specification.

 

When using VESDA ECO with the VESDA VFT-15 or ICAM IFT-15 detectors a 
special adapter is required, part number ECO-FT15.

Installation Instructions

To fix the detector to the pipe work, follow these steps:

1. 

Ensure that any glue used in fixing the sample pipes has been given sufficient time to 

cure such that any vapours from the glue will not affect the gas detection before fitting 

the ECO detector. 

2.  Remove a straight section from the pipe at the preferred location within the pipe work. 

The exact length of pipe to be removed depends on the tolerances of the pipe-work 

being used, but as a guide the lengths are approximately: 

• 

60 mm when installing in a 25 mm OD pipe

•  4 inches (100 mm) when installing in a ¾” BSP pipe

3.  Ensure that the cuts on the pipe are perpendicular to the pipe and that there are no 

burrs or sharp edges present. If so, trim the pipe to remove them. Ensure the pipe is 
free of any debris. 

4. 

Verify the correct orientation of the ECO detector, in that the flow arrow on the side of 

the ECO enclosure is in the same direction as the sample airflow.

5.  Insert the detector into the open section of the pipe, ensuring that the pipe entry to the 

detector is square and the pipes sit correctly in the tapered air inlet/outlet ports and 
provide an air tight seal.

Note:

  

Do not glue the pipes to the detector. This is not necessary and is an obstacle 
to future maintenance. 
If the gas test port is not to be permanently connected to a remote gassing 

pipe, ensure that the blanking plug supplied with the unit is fitted firmly in place. 

Alternatively, if a permanent remote gassing pipe is to be installed, use 6 mm 

OD pipe fitted into the gas test port of the ECO at one end and ensure the 

opposite end is fitted with a gas tight plug during normal operation.

6.  Ensure that the device is oriented such that the status indicators are visible for 

inspection purposes.

7. 

Ensure that there is sufficient access to the enclosure cover such that it can be 

removed and the sensor cartridge accessed. 

8. 

During calibration no flow should pass through the ECO detector. Installing a shut 

off isolation valve in front of the ECO detector and shutting the aspirator off during 
calibration will help achieve this result. Ensure that the valve does not restrict the inside 
diameter of the sample pipe. Installing a clean out tee in front of the valve to facilitate 
routine pipe network cleaning, without having to remove the ECO detector or pipe is 
also recommended.

www.acornfiresecurity.com

www.acornfiresecurity.com

Reviews: