• The GD-3000 Combustible Gas Detector mounts on a standard 4x4 electrical box and
becomes cover for the box
• Supervised system: any internal detector problem will cause the fan & alarm relay to
activate
• Optional calibration kit is available. One screw allows access for calibration
2.4 Specifications
• Power: 3W (max) from 12 to 24VAC (Volts Alternating Current) or 12 to 48VDC (Volts
Direct Current)
• Current @ 24VDC: 75mA in alarm (two relays), 50mA (fan relay only)
• Shipping Weight: 1 pound (0.45 kg)
• Size: 4 1/2 x 4 x 2 1/8 in. (11.4 x 10.2 x 5.4 cm)
• Color: dark gray
• Connections: plugs/terminals
• Mounting box: (not included) 4x4 electric
• Fan relay: 5A, 240VAC, pilot duty, SPDT
• Fan relay actuation: selectable at 1, 2, 3, 4, 5, 6, 7, 8, 9, 10 (default), 11, 12, 13, 14,
15, 16, 17, 18, 19, 20% LEL
• Fan Delay Settings of 0, 1, 3 (default), 5 and 10 minutes
• Fan Minimum Run Time settings are OFF (default), 3, 5, 10 or 15 minutes
• Alarm relay: 0.5A 200V, 10VA
• Alarm relay actuation: selectable N.O. default or N.C.
• Alarm relay settings: OFF, 5, 10, 15, 20 (default), 25% LEL
• Current loop, 4-20mA for 0-50% LEL
• Operating environ: 0°F to 125°F (-18°C to 52°C). 10 to 90% RH
3. INSTALLATION AND OPERATING INSTRUCTIONS
The following instructions are intended to serve as a guideline for the use of the Eagle
Eye GD-3000 Combustible Gas Detector, Controller and Transducer. It is not to be
considered all-inclusive, nor is it intended to replace the policy and procedures for each
facility.
WARNING
This detector monitors for the presence and concentration level of certain specified
airborne gases. Misuse may produce an inaccurate reading, which means that higher
6