Eagle Eye GD-3000 User Manual
3.5 Operation
1. With the display function turned “On”, the Eagle Eye GD-3000 Combustible Gas
Detector will show the current concentration of gas % LEL or “0” (zero) in clean air.
When the gas concentration reaches the Fan Relay setting (10% LEL, for example) the
display will flash back and forth between “FAn” and “10”. With the display function
turned ”Off”, the display does not show the gas concentration, but will show “FAn” as
long as the fan relay is activated.
2. With the display function turned “On” and the gas concentration reaching the alarm
relay setting, (20% LEL, for example) the display will flash back and forth between “ALr”
and “20”. The buzzer will sound indicating “Alarm” if the buzzer is turned “On”. With the
display function turned off the display does not show the gas concentration, but will
show “ALr” when the Alarm relay is activated.
3. With the 4-20mA function turned “On”, the 4-20mA output will correspond to the
concentration (0-50% LEL). The display will show “FAn” and “ALr” and sound as
outlined above.
3.6 Default Configuration – Factory Settings
• The default Display setting is Off
• The default Power Up Test setting is On
• The default Buzzer setting is Off
• The default Alarm Relay setting is activation at 20% LEL
• The default Fan Relay Delay setting is 3 minutes
• The default Fan Minimum Runtime setting is OFF
• The default Fan Relay setting is activation at 10% LEL
• The default Alarm Relay Configuration is Normally Open
• The default 4-20mA Output setting is OFF
To change settings, remove the Philips screw on the front of the Eagle Eye GD-3000
Combustible Gas Detector. Pull off the front cover of the unit.
Gas Selection
To select the
Gas Option
, in normal mode, press the
Next
button once to display the
current gas selection (
mE is Methane, Pro is Propane and Hy is Hydrogen)
. Then
press the
Enter
button twice to enter the selection menu. The currently selected
gas will
be shown on the display. Press
Next
to scroll through the available gases selections.
The selected gas will be flashing,
press
Enter
to select the gas and
Enter
again to
confirm the selection. To return back to normal mode press
Next
until “End” is
displayed
and press
Enter
.
12