F a u l t s a n d s o l u t i o n s
EC6000
9
.
Function Code Table
P0
Standard Parameter group
0000H
Address
Function
Code
P0
-
00
AC drive rated
G/P type
selection
Setting Range
0: heavy load rating (G) constant torque
application
1: light load rating (P) decreasing torque
application
P0
-
01
P0
-
02
P0
-
03
P0
-
05
P0
-
04
P0
-
07
Command source
selection
Auxiliary
frequency
source Y
selection
Motor control
mode
Main frequency
source X
selection
Main source
X Gain
Main and
Auxiliary
frequency
source
combination
mode
0001H
0002H
0003H
0005H
0004H
0007H
0: V/F control
(direction LED is on)
1: Sensorless flux vector control(SVC)
(direction LED slow blinking)
2: Closed-loop vector control(FVC)
(direction LED fast blinking)
0: Operation panel control (LOC LED on)
1: Terminal control (REM LED on)
2: RS485 Communication control (REM LED
blinking)
3: Option card (REM LOC LED on)
4: Terminal switchover (REM LOC LED
blinking)
0: Operation panel digital setting frequency
1: AI1 2: AI2 3: AI3
4:Terminal pulse HS setting
5: RS485 communication setting
6: UP/DW setting 7: PID control setting
8: PLC mode operation setting 9: reserved
A: reserved B: Option card
C: Terminal switchover
Same as P0-03
0.000
~
5.000
0:Main frequency source X is valid
1:Auxiliary frequency source Y is valid
2:X+Y
3:X-Y
4:MAX(|X|,|Y|) 5:MIN(|X|,|Y|)
6:X*Y
7:Any non-zero value of the main frequency
source X and auxiliary frequency source Y is
valid,and the primary channel takes
precedence.
Default
0
0
0
0
1.000
0
Auxiliary
source Y Gain
P0
-
06
0006H
0.000
~
5.000
1.000
0
Parameter Name
0008H
P0
-
08
Digital
setting of
main source X
frequency
0.00~Maximum output frequency
50.00Hz
F u n c t i o n C o d e T a b l e
0009H
P0
-
09
Digital
setting of
auxiliary
source Y
frequency
0.00~Maximum output frequency
P0
-
10
P0
-
11
P0
-
12
P0
-
13
P0
-
17
P0
-
15
P0
-
18
Source of
frequency
upper limit
selection
Acceleration
time 1
Acceleration/
Deceleration
time unit
Maximum output
frequency
Source of
frequency
upper limit
digital setting
Source of
frequency
lower limit
digital setting
Stopping
method
000AH
000BH
000CH
000DH
000FH
0011H
0012H
Carrier
frequency
0.00~320.00Hz
0: Set by P0-12 1: AI1 2: AI2 3: AI3
4: Terminal pulse setting
5: RS485 Communication setting
0.1~6500.0s
0~100.0%
1: 0.1s
2: 0.01s
0: Ramp to stop
1: Coast to stop
0~100
.
0
%
50.00Hz
50.00Hz
0
100.0%
0
.
0
%
P0
-
14
Frequency
lower limit
run mode
000EH
0: Run at frequency lower limit
1: Stop
2: Run at zero speed
1
Model
dependent
0
1
Rotation
direction
selection
P0
-
19
0013H
BIT0:
0: Forward direction operation
1: Reverse direction operation
BIT1:
0: Reverse operation enable
1: Reverse operation disable
00
P0
-
20
1.0~15.0KHz
0014H
Model
dependent
P0
-
16
Deceleration
time 1
0010H
0.1~6500.0s
Model
dependent
Frequency
reference
resolution
P0
-
21
1:0.1Hz
2:0.01Hz
0015H
2
P0
-
22
Reserved
0016H
P0
-
23
Parameter
initialization
0017H
-
0:No operation
1:Data locked
2:Reset Error message
3~6:Undefined
7:Initialization setting—User data reset
10:Back up current user parameters
210:Restore user backup parameters
-
0~210