background image

3 6

 -

37

 -

  F u n c t i o n C o d e T a b l e

EC6000

 

  F u n c t i o n C o d e T a b l e

EC6000

 

0.0~60.0s 

P9

-

41

Over-speed 

detection time

1.0s

0929H

0.0~50.0%(Maximum frequency) 

P9

-

42

Detection value of 

too large speed 

deviation

20.0%

092AH

0.0~60.0s 

P9

-

43

Detection time of 

too large speed 

deviation

5.0s

092BH

0~100  

P9

-

44

Overvoltage 

stall gain

0%

092CH

120~150%  

P9

-

45

130%

092DH

Overvoltage stall 

protective voltage

0~100 

P9

-

46

Overcurrent 

stall gain

20

092EH

P9-47

P9-48

P9-49

100

200%

1

200%

2

250.0s

BIT0: Motor overload (Err11) action select
0: Immediately-stop, fault alarm
1: Emergency stop, fault alarm 
2: Only warning, AC drive continues to 
operate
BIT1: Input phase loss (Err12) action select
Same as BIT0
BIT2: Output phase loss (Err13) action 
select
Same as BIT0
BIT3: External fault (Err15) action select
Same as BIT0
BIT0: Abnormal communication (Err16) action 
selection
Same as P9-50 BIT0
BIT1: Encoder failure (Err20) action select
0: Immediately-stop, fault alarm
1: Emergency stop, fault alarm 
2: Switch to VF, continue operation
BIT2: Function code reading and writing 
abnormal (Err21) action selection
0: Immediately-stop, fault alarm
1: Emergency stop, fault report
BIT3: Motor overheating (Err25) action 
select
Same as BIT0

092FH

0930H

0931H

0932H

0933H

150%

20%

8s

0000

0000

P9-50

P9-51

Overcurrent 

stall protective 

current

Input phase loss 
protection level

Input phase loss 
protection delay

Protection 

action 

selection 1

Protection 

action 

selection 2

P9

-

52

Protection 

action 

selection 3

0000

0934H

BIT0: User defined fault 1 (Err27) action 
selection
Same as P9-50 BIT0
BIT1: User defined fault 2 (Err28) action 
selection
Same as BIT0

BIT2: Power on time arrival (Err29) action 
selection
Same as BIT1
BIT3: Load loss (Err30) action selection 
0: Immediately-stop, fault alarm
1: Emergency stop, fault alarm  
2: Directly jump to 7% of the rated frequency 
of the motor to continue operation, and 
automatically return to the set frequency 
operation during noload operation

P9

-

52

Protection 

action 

selection 3

0000

0934H

PA

 

Process PID control parameters

BIT0: Loss of PID feedback during operation 
(Err31) action selection
Same as PB-01 BIT0
BIT1: Excessive speed deviation (Err42) 
action selection
Same as BIT0
BIT2: Motor over speed (Err43) action 
selection
Same as BIT0
BIT3: Initial position error (Err51) action 
selection
Same as BIT0

BIT0: Speed feedback error (Err52) action 
selection
Same as PB-01 BIT0
BIT1: Reserved
BIT2: Reserved
BIT3: Reserved

0: PID setting source
1: AI1      2: AI2     3: AI3 
4: Terminal pulse setting(PUL) 
5: Communication setting 
6: PLC setting    

 

     

7: UP/DW control

   

     

8: Terminal selection

0.00

PA-05

Setting Range

0935H

0936H

0A00H

0A01H

Address

0000

0

0

0.5Mpa

Default

 

P9-53

P9-54

PA

-

00

PA

-

01

Function 

Code

Protection 

action 

selection 4

Protection 

action 

selection 5

PID setting 

source

PID digital 

setting

Parameter Name

0~100

0937H

40

P9-58

Instantaneous
stop and non-

stop gain Kp

Instantaneous
stop and non-
stop integral

coefficient Ki

P9-59

0~100

0938H

30

PA

-

02

PID control 

feedback 

signal source

0: PID setting source

 

  

1: AI1    
2: AI2   
3: AI3        
4: Terminal pulse feedbac

0A02H

2

Summary of Contents for EC6000 Series

Page 1: ...2 1 in 2023 Copyright subject to change without notice Professional AC Drive Manufacturer ZHEJIANG EACN ELECTRONIC TECHNOLOGY CO LTD Address No 1 Jinhe Road Qinshan Street Haiyan County Jiaxing City Z...

Page 2: ...by high voltage Never connect the main circuit output terminals U V and W directly to the AC main circuit power supply The circuit board of the AC drive has CMOS IC which is extremely easy to be dama...

Page 3: ...ation Description of AC drive EC6000 Voltage 220V Voltage 380V Power kW Rated output current A 0 75 1 5 2 2 4 0 5 5 11 7 5 15 18 5 30 22 37 45 55 75 110 90 132 160 200 220 250 280 315 400 350 3 4 4 8...

Page 4: ...he CLVC mode High performance Power dip ride through Control of asynchronous motor and synchronous motor are implemented through the high performance current vector control technology The load feedbac...

Page 5: ...rip or salt Altitude Ambient temperature Lower than 1000m Display and operation on the operation panel Optional parts LCD operation panel braking unit I O extension card 1 I O extension card 2 user pr...

Page 6: ...9 D1 174 194 194 Installation Hole 4 5 6 7 9 30kW 191 120 471 450 242 232 9 0 75kW 1 5kW 2 2kW 4 0kW 5 5kW 11kW 22kW Structure A Structure 380V Class A Structure B Structure 0 75kW 105 94 160 150 137...

Page 7: ...utput Terminal Commun ication Function Description Voltage or current output is decided by P5 32 Output voltage range 0V 10V Output current range 0mA 20mA Contact driving capacity 250Vac 3A COS 0 4 30...

Page 8: ...aking unit and braking resistor Err04 Overcurrent at constant speed 1 The output circuit is grounded or short circuited 2 Motor auto tuning is not performed 3 The input voltage is too low 4 A sudden l...

Page 9: ...is damaged 4 The PG card is faulty 1 Set the encoder type correctly based on the actual situation 2 Eliminate external faults 3 Replace the damaged encoder 4 Replace the faulty PG card Err21 Err22 EE...

Page 10: ...e primary channel takes precedence Default 0 0 0 0 1 000 0 Auxiliary source Y Gain P0 06 0006H 0 000 5 000 1 000 0 Parameter Name 0008H P0 08 Digital setting of main source X frequency 0 00 Maximum ou...

Page 11: ...C Drive 55kW 0 1A P1 04 AC Drive 55kW Model dependent P1 12 P1 16 Reserved 010CH 0110H P1 23 Encoder type BIT0 Encoder type 0 ABZ incremental encoder 1 UVW incremental encoder 2 Resolver 3 SIN COS enc...

Page 12: ...05 P3 06 P3 07 P3 08 P3 09 Parameter Name V F curve selection Multi point V F frequency1 F1 Multi point V F voltage1 V1 Multi point V F frequency2 F2 Multi point V F voltage2 V2 Multi point V F freque...

Page 13: ...11 Terminal YWN 12 UP and YWN setting clear 13 Speed control Torque control switchover 14 Speed search start enable 15 Reserved 16 Multi reference terminal 1 17 Multi reference terminal 2 18 Multi re...

Page 14: ...ode after fault reset 0 The terminal operation command is valid immediately 1 The terminal operation command is valid only after it is canceled P4 16 P4 17 P4 18 Terminal protection function selection...

Page 15: ...100 00 100 00 0509H P5 10 AI2 filter time 0 00 10 00s 0 10s 050AH P5 11 AI3 input voltage minimum value 0 00 10 00V 0 00V 050BH P5 12 AI3 input voltage lower limit corresponding setting 0 00 100 00 0...

Page 16: ...0 Straight line 1 Curve 0 150 0 00 50 00Hz P6 09 P6 10 P6 11 P6 13 P6 12 P6 08 0609H 060AH 060BH 060DH 060CH 0608H 0 00Hz 0 0 0s 0 0s 00 0 Start of S curve acceleration time End of S curve acceleratio...

Page 17: ...rs Accumulated running days Accumulated running hours Read only Read only Read only Read only 070BH 0 Chinese 1 English BIT1 Output frequency display selection 0 Target frequency displays the target f...

Page 18: ...perature reached 0 100 0 65000 BIT0 Motor overload protection selection 0 Invalid 1 Valid BIT1 Ground fault duringpower on 0 Invalid 1 Valid BIT2 Input phase loss protection selection 0 Invalid 1 Vali...

Page 19: ...00 0A P9 17 Output voltage upon 2nd fault 0911H 0 3000V Read only Read only Read only Read only Read only Read only 0 3000V P9 18 AC drive status upon 2nd fault 0912H Same as P9 10 P9 19 S terminal st...

Page 20: ...2 P9 52 Protection action selection 3 0000 0934H BIT0 User defined fault 1 Err27 action selection Same as P9 50 BIT0 BIT1 User defined fault 2 Err28 action selection Same as BIT0 BIT2 Power on time ar...

Page 21: ...help to reduce PID overshoot PA 07 0A07H 00 BIT0 PID shutdown operation 0 Shutdown without calculation 1 Operation when shutdown BIT1 Constant pressure water supply sleep function 0 Invalid 1 Valid B...

Page 22: ...e first set of transmission frame selection 0 Invalid 1 Run command setting 2 Master set frequency 0031 0B09H 3 Master output frequency 4 Master upper limit frequency 5 Master set torque reserved 6 Ma...

Page 23: ...0DH 80 0 PD 13 Multi frequency 14 0D0EH 60 0 PD 14 Multi frequency 15 0D10H 10 0 PD 16 Running time of PLC reference 1 0D0FH 0000 PD 15 PLC running mode BIT0 Circulation mode 0 Stop after the AC drive...

Page 24: ...H 00 PD 39 Running direction and acceleration deceleration time of PLC reference 9 0D28H 00 PD 40 Running direction and acceleration deceleration time of PLC reference 10 0D29H 00 PD 41 Running direct...

Page 25: ...A3 03 0 Function code P5 11 setting 1 AI1 2 AI2 3 AI3 4 PULSE setting 5 Communication setting 6 MIN AI1 AI2 7 MAX AI1 AI2 The full range of 1 7 option corresponds to P5 11 A0 01 Torque setting source...

Page 26: ...48 00Hz 25 00Hz A1 11 A1 12 Add pump frequency 2 Reduce pump frequency 2 0 00 maximum frequency 0 00 A1 11 110BH 110CH 48 00Hz 25 00Hz A1 13 A1 14 Add pump frequency 3 0 00 maximum frequency 0 00 A1 1...

Page 27: ...s Application mode 1 EC6000 series AC drive has a single master and multi slave control network connected to RS485 bus When the master uses the broadcast command slave address is 0 the slave does not...

Page 28: ...ieces bytes transmit time START Sub machine address Order code Bytes quantity low position Data address 2100H high position 3 5 pieces bytes transmit time 01H 03H 06H 13H 88H 00H 00H Data address 2100...

Page 29: ...data bit the number of whole 1 in 1 1 0 0 0 1 0 1 is 4 pieces if use even verifica tion the odd even verification bit of frame will be 0 then obtain the quan tity of whole 1 still be 4 also not proce...

Page 30: ...inal control 2 RS485 control 3 Option card 4 Terminal switchover AC drive operation status 2100H R BIT0 BIT1 BIT2 BIT3 BIT4 BIT5 BIT6 BIT7 10 W Motor control mode 0 V F mode 1 SVC control 2 FVC contro...

Page 31: ...W Note 1 The function descriptions in brackets are the factory value of AC drive 2 Opticalcoupler isolation compatible ambipolarity input 3 Input impedance 2 4kO 4 Voltage range at electrical level in...

Page 32: ...uality inverter Warranty Card User Name User Address User Contact Tel Specification Number Distributor Contacts Date of delivery Address No 1 Jinhe Road Qinshan Street Haiyan County Jiaxing City Zheji...

Reviews: