22
Power rate limit modes as required by AS/NZS 4777.2:2020 is supported in
this inverters. When a demand response mode (except for DRM 0) is
asserted or unasserted the power rate limit will apply to the increase or
decrease in power generation or consumption and the transitions
between power levels.
When a DRED is connected to an inverter, the inverter will receive and
response to the outside signal directly. And the DRM working mode will be
shown in the BASIC INFO in the LCD menu.
5.12 Remote Disconnection and Re-connection
The Inverters are designed with the function of remote disconnection and
re-connection. To use this function, a Wi-Fi or 4G data logger stick has to
be fixed to the Wifi port and work properly. The pin 2 and pin 3 of the data
logger stick are allocated for this function. Then the remote disconnection
and reconnection can be achieved by sending instruments through the
monitoring App Solarman Business.
6. Operation
6.1 Start and Stop Inverters
6.1.1 Inverter Turning-on
The following procedures have to be followed exactly to start an inverter.
1) Turn on the AC breaker.
2) Turn on the DC Switch.
3) After a compulsory delay of 30 to 300 seconds, the inverter will start
to work and the POWER light will be on.