10
times of the weight of the inverters.
The location shall be convenient for electrical connection, operation
and maintenance.
The ingress protection of the inverter is IP66, so it can be installed
both indoors and outdoors.
The temperature of the cooling fin may exceed 75
℃,
so select safe
locations.
The location must be well ventilated and sheltered from direct
sunlight, rain or snow.
Ensure the visibility of the LED lights and LCD display on the front
panel of inverters.
Install inverters vertically or with a backward tilt within 15 degrees.
No lateral tilt is allowed.
If more than one inverter are installed in one location, a minimum
150 mm clearance should be kept between two inverters and a
minimum 300 mm clearance between inverters and the ground.
The Inverter is to be installed in a high traffic area where the fault is
likely to be seen.