User Manual EE872 Modular Probe for CO

2

, RH, T and p

4  Installation

Best measurement performance is achieved when the entire probe is located inside the environment to 

be monitored. This is the case, for example, when the EE872 is fixed onto a wall with the 

mounting clip 

HA010227

 (not included in the scope of supply, see data sheet “Accessories”), or freely hangs from the 

ceiling on the connection cable.

The probe can be installed also into a partition wall using the stainless steel 

mounting flange 

HA010226

 (not included in the scope of supply, see data sheet “Accessories”). 

For large temperature difference between the two sides of the wall, T gradients may appear along the 

probe. Although the CO

2

 measurement is T compensated, these gradients have a great impact on the 

RH and T accuracy in the M13 model. Therefore, it is of paramount importance to minimize the tempe-

rature gradients. The part of the probe standing out of the wall on the connection side shall be as small 

as possible and well thermally insulated.

For best RH and T accuracy, model M13 shall be installed horizontally or with the filter cap positioned 

downwards.

EE872 with mounting clip 

HA010227

EE872 with mounting flange 

HA010226

For outdoor applications the EE872 must be used with the radiation shield HA010510 (not included in 

the scope of supply, see data sheet “Accessories”), which protects the device against rain, snow, ice 

and solar radiation.

5  Setup and Adjustment

The EE872 is ready to use and does not require any configuration by the user. The factory setup of 

EE872 corresponds to the type number ordered. Please see chapter 3.1 for a model overview and the 

data sheet at 

www.epluse.com/EE872

. The user can change the factory setup by using the Modbus 

configuration adapter (order code HA011018) and the EE-PCS Product Configuration Software.
One can change the CO

2

 output signal type (analogue to digital and vice versa), the analogue output 

scaling and the digital settings. For p measurement, an offset correction is possible. The CO

2

, RH and T 

measurement is offset and 2-point adjustable.
In addition, it is possible to enable or disable the pressure compensation (factory setting: enabled), the 

sensing module heating (factory setting according to the model ordered) and the NAMUR error indication 

(factory setting: disabled).

Please note:

 The EE872 may not be connected to any additional power supply when using the Modbus 

configuration adapter HA011018.

PC

Fig. 4  Modbus configuration adapter HA011018

Summary of Contents for EE872 Series

Page 1: ...BA_EE872_e V1 2 technical data are subject to change User Manual EE872 Modular Probe for CO2 RH T and p...

Page 2: ...equipment has been tested and found to comply with the limits for a Class A digital device pursuant to part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmf...

Page 3: ...put and RS485 Interface 7 4 Installation 8 5 Setup and Adjustment 8 5 1 EE PCS Product Configuration Software 9 5 2 Digital Interface RS485 with Modbus RTU Protocol 9 5 2 1 Digital Settings 9 5 2 2 Mo...

Page 4: ...nce In any case the scope of liability is limited to the corresponding amount of the order issued to the manufacturer The manufacturer assumes no liability for damages incurred due to failure to compl...

Page 5: ...vices are not accidentally used by marking them clearly as faulty A faulty device may only be investigated and possibly repaired by qualified trained and authorized staff If the fault cannot be fixed...

Page 6: ...ng is activated the RH and T data is not available The calculated Td value is still available All values are available on the digital interface All versions provide CO2 measurement T and p compensated...

Page 7: ...n pin not connected EE872 set to RS485 interface option P1 in the order code features RS485 interface EE872 set to analogue outputs option GA7 or GA11 in the order code the RS485 interface is active f...

Page 8: ...with mounting clip HA010227 EE872 with mounting flange HA010226 For outdoor applications the EE872 must be used with the radiation shield HA010510 not included in the scope of supply see data sheet A...

Page 9: ...Device address baud rate parity and stop bits can be set via 1 EE PCS Product Configuration Software and the Modbus configuration adapter HA011018 The EE PCS can be downloaded free of charge from www...

Page 10: ...FA1 Temperature T F 50 4003 0xFA2 Temperature T K 50 4005 0xFA4 Dew point temperature Td C 100 4053 0xFD4 Dew point temperature Td F 100 4054 0xFD5 Dew point temperature Td K 100 4074 0xFE9 Tab 3 Inte...

Page 11: ...abled by factory default can be enabled with the EE PCS Product Configuration Software see above Output signal NAMUR signal level 0 5 V 5 5 V 0 10 V 11 V 4 20 mA 21 mA 0 20 mA 21 mA 6 Maintenance 6 1...

Page 12: ...rotection cap rubber caps Fig 6 Calibration adapter HA010785 with mounted rubber caps for use as protection cap Procedure Remove the filter cap and install the calibration adapter onto the probe Conne...

Page 13: ...range 40 60 C 40 140 F Accuracy3 5 60 C 41 140 F typ 0 5 C 0 9 F Outputs Analogue CO2 only 0 5 V 0 10 V 1 mA Load current 1 mA 0 20 mA 4 20 mA 3 wire Load resistance 500 Ohm Digital interface CO2 RH T...

Page 14: ...0 6460 Office Stuttgart Tel 49 151 538 37 500 E E Elektronik Italy info epluse it Tel 39 02 2707 86 36 E E Elektronik France info epluse fr Tel 33 4 74 72 35 82 E E Elektronik USA office epluse com Of...

Reviews: