9
User Manual EE872 Modular Probe for CO
2
, RH, T and p
5.1 EE-PCS Product Configuration Software
1. Download the EE-PCS Product Configuration Software from
install it on the PC.
2. Connect the E+E device to the PC using the Modbus configuration cable.
3. Start the EE-PCS software.
4. Follow the instructions on the EE-PCS opening page for scanning the ports and identifying the
connected device.
5. Click on the desired setup or adjustment mode from the main EE-PCS menu on the left and follow
the online instructions of the EE-PCS
5.2 Digital Interface RS485 with Modbus RTU Protocol
5.2.1 Digital Settings
Factory settings
User selectable values (via EE-PCS)
Baud rate
9600
9600, 19200, 38400
Data bits
8
8
Parity
Even
None, odd, even
Stop bits
1
1, 2
Slave address
237
1...247
Tab. 1 Data transmission
The recommended settings for multiple devices in a Modbus RTU network are 9600, 8, even, 1
The EE872 represents 1/10 unit load on an RS485 network.
Device address, baud rate, parity and stop bits can be set via:
1.
EE-PCS, Product Configuration Software and the Modbus configuration adapter HA011018.
The EE-PCS can be downloaded free of charge from
2. Modbus protocol in the register 60001 (0x00) and 60002 (0x01). See Application Note Modbus
AN0103 (available on
The serial number as ASCII-code is located at read register address 30001-30008 (16 bit per address).
The firmware version is located at register address 30009 (bit 15...8 = major release; bit 7...0 = minor
release). The sensor name is located at register address 30010.
INTEGER 16 bit
Parameter
Register number
1)
[DEC]
Protocol address
2)
[HEX]
Read and write register: function code 0x03 / 0x06
Slave-ID Modbus address
0001
0x00
Modbus protocol settings
3)
0002
0x01
INFO (read register):
Parameter
Register number
1)
[DEC]
Protocol address
2)
[HEX]
Read and write register: function code 0x03 / 0x04
Serial number (as ASCII)
0001
0x00
Firmware version
0009
0x08
Sensor Name
0010
0x09
1) Register number starts from 1.
2) Protocol address starts from 0.
3) For Modbus protocol settings see Application Note Modbus AN0103 (available on