background image

HEADQUARTERS

E+E Elektronik Ges.m.b.H.

Langwiesen 7
A-4209 Engerwitzdorf
Austria
Tel: +43 7235 605 0
Fax: +43 7235 605 8
[email protected]
www.epluse.com

SUBSIDIARIES

E+E Elektronik Germany

[email protected]

Office Bad Homburg

Tel: +49 6172 13881-0

Office Hamburg

Tel: +49 160 9050 6460

Office Stuttgart

Tel: +49 151 538 37 500

E+E Elektronik Italy

[email protected]
Tel: +39 02 2707 86 36

E+E Elektronik France

[email protected]
Tel: +33 4 74 72 35 82

E+E Elektronik USA

[email protected]

Office Boston

Tel: +1 847 490 0520 

Office Chicago

Tel: +1 847 490 0520

E+E Elektronik Korea

Tel: +82 31 732 6050 
[email protected]

E+E Elektronik China

[email protected]

Office Beijing

Tel: +86 10 8499 2361

Office Shanghai

Tel: +86 21 6117 6129

Office Guangzhou

Tel: +86 20 3898 7052

Summary of Contents for EE872 Series

Page 1: ...BA_EE872_e V1 2 technical data are subject to change User Manual EE872 Modular Probe for CO2 RH T and p...

Page 2: ...equipment has been tested and found to comply with the limits for a Class A digital device pursuant to part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmf...

Page 3: ...put and RS485 Interface 7 4 Installation 8 5 Setup and Adjustment 8 5 1 EE PCS Product Configuration Software 9 5 2 Digital Interface RS485 with Modbus RTU Protocol 9 5 2 1 Digital Settings 9 5 2 2 Mo...

Page 4: ...nce In any case the scope of liability is limited to the corresponding amount of the order issued to the manufacturer The manufacturer assumes no liability for damages incurred due to failure to compl...

Page 5: ...vices are not accidentally used by marking them clearly as faulty A faulty device may only be investigated and possibly repaired by qualified trained and authorized staff If the fault cannot be fixed...

Page 6: ...ng is activated the RH and T data is not available The calculated Td value is still available All values are available on the digital interface All versions provide CO2 measurement T and p compensated...

Page 7: ...n pin not connected EE872 set to RS485 interface option P1 in the order code features RS485 interface EE872 set to analogue outputs option GA7 or GA11 in the order code the RS485 interface is active f...

Page 8: ...with mounting clip HA010227 EE872 with mounting flange HA010226 For outdoor applications the EE872 must be used with the radiation shield HA010510 not included in the scope of supply see data sheet A...

Page 9: ...Device address baud rate parity and stop bits can be set via 1 EE PCS Product Configuration Software and the Modbus configuration adapter HA011018 The EE PCS can be downloaded free of charge from www...

Page 10: ...FA1 Temperature T F 50 4003 0xFA2 Temperature T K 50 4005 0xFA4 Dew point temperature Td C 100 4053 0xFD4 Dew point temperature Td F 100 4054 0xFD5 Dew point temperature Td K 100 4074 0xFE9 Tab 3 Inte...

Page 11: ...abled by factory default can be enabled with the EE PCS Product Configuration Software see above Output signal NAMUR signal level 0 5 V 5 5 V 0 10 V 11 V 4 20 mA 21 mA 0 20 mA 21 mA 6 Maintenance 6 1...

Page 12: ...rotection cap rubber caps Fig 6 Calibration adapter HA010785 with mounted rubber caps for use as protection cap Procedure Remove the filter cap and install the calibration adapter onto the probe Conne...

Page 13: ...range 40 60 C 40 140 F Accuracy3 5 60 C 41 140 F typ 0 5 C 0 9 F Outputs Analogue CO2 only 0 5 V 0 10 V 1 mA Load current 1 mA 0 20 mA 4 20 mA 3 wire Load resistance 500 Ohm Digital interface CO2 RH T...

Page 14: ...0 6460 Office Stuttgart Tel 49 151 538 37 500 E E Elektronik Italy info epluse it Tel 39 02 2707 86 36 E E Elektronik France info epluse fr Tel 33 4 74 72 35 82 E E Elektronik USA office epluse com Of...

Reviews: