22
US-Unit
Analogue output
[0...10 V / 0(4)...20 mA]
from
to
unit
low
(L1)
high
(H1)
standardized
DN15:
0
35 70 SCFM
volumetric
flow DN20:
0 60
120
SCFM
DN25:
0 100
200
SCFM
DN32:
0 165
330
SCFM
DN40:
0 260
520
SCFM
DN50:
0 410
820
SCFM
mass
flow
DN15:
0 75
150
kg/h
DN20:
0 140
280
kg/h
DN25:
0 220
440
kg/h
DN32
0 360
720
kg/h
DN40:
0 570
1140
kg/h
DN50:
0 890
1780
kg/h
standardized
flow
≤DN50
0
20000
40000
SFPM
Temperatur
alle Ø
-4
176 176 °F
Switching output
[switching point/hysteresis]
standardized
DN15
30/3 60/6 SCFM
volumetric
flow DN20
50/5
100/10
SCFM
DN25:
80/8
160/16
SCFM
DN32:
130/13
260/26
SCFM
DN40:
210/21
420/42
SCFM
DN50:
330/33
660/66
SCFM
mass
flow
DN15:
60/6
120/12
kg/h
DN20:
110/11
220/22
kg/h
DN25:
200/20
400/40
kg/h
DN32:
290/29
580/58
kg/h
DN40:
460/46
920/92
kg/h
DN50:
700/70
1400/140
kg/h
standardized flow
≤DN50
15000/1500
30000/3000
SFPM
temperature
all Ø
90/9
150/15
°F
Pulse output
pulse-value = 1CF
pulse-duration = 0.1 sec.
CONFIGURATION SOFTWARE
LIMITED LIABILITY
E+E Elektronik shall not be held liable for any damages or consequential damages (for example, but not
restricted to, loss of earnings, interruption of business, loss of information and data or any other financial
losses) resulting from the installation, use or impossibility of use of an E+E Elektronik software product and
any associated support services or non-performance of support services.
1.
General
The configuration software can be downloaded free of charge at
www.epluse.com/ee771
The configuration software, allows for a user-friendly adaptation of the flow meter to the application. In addi-
tion, the measurement values for flow and temperature can be calibrated / adjusted.
The system requirements for the installation and execution of the software are:
•
Windows XP with SP3, Windows Vista or Windows 7
•
.NET framework 3.5 with SP1
•
USB 2.0 interface
During setup there will be no installation of .NET Framework 3.5 SP1 – if the required version is not already
installed on the computer the following error message will appear at the start of the configuration software.
.NET Framework 3.5 SP1 can be installed using Windows Update.