User Manual EE610 Low Differential Pressure Sensor

2x Ø2.2

Ø 

6.5

80

18.5

60∞

Ø16

Ø7

Ø 

7.3

Fig. 8 

Dimension of pressure connection nipples

•  Install first the pressure connection nipples (included in the scope of supply) onto the duct. 

Use a Ø 7.5 mm drill.

•  Connect the pressure hose (included in the scope of supply) first to the EE610 and then to the nipples 

at the duct. Route the pressure hose for avoiding sharp bends which might lead to the hose  

obstruction („Fig. 9 Pressure hose route“).

Fig. 9 

Pressure hose route

Important: Make sure to connect the higher pressure at the “+” pressure connector and the lower 

pressure at the “-“ pressure connector. Inverted connection leads to “out of range” information on the 

optional display and at the analogue outputs, see „4.1.6 Outputs“ and „7.2.3 Out of range“. 

6  Maintenance and service

EE610 does not require any special maintenance, nevertheless it is recommended to perform a zero 

point adjustment every 12 month. If needed, the enclosure may be cleaned and the device may be 

re-adjusted as described below.

6.1  Cleaning

Use a damp soft cloth to remove deposits of dust or dirt from the exterior of the device and from the 

display. Do not attempt to clean the interior of the device. Do not use any solvents, alcohol or abrasive 

cleaning agents.

6.2  Repairs

Repairs may be carried out by the manufacturer only. The attempt of unauthorised repair excludes any 

warranty claims. 

Summary of Contents for EE610

Page 1: ...BA_EE610_e v1 1 technical data are subject to change User Manual EE610 Low Differential Pressure Sensor...

Page 2: ...and found to comply with the limits for a Class A digital device pursuant to part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference when the...

Page 3: ...put signal with S8 8 4 1 6 Outputs 8 4 2 Digital version 8 4 2 1 EE PCS Product Configuration Software 9 4 2 2 RS485 Digital Interface settings 9 4 2 3 BACnet Protocol Settings 9 4 2 4 Modbus Protocol...

Page 4: ...E610 in explosive atmosphere or for measurement of aggressive gases Do not apply the nominal voltage to the output terminals 1 1 2 Mounting start up and operation The EE610 differential pressure senso...

Page 5: ...Environmental aspects Products from E E Elektronik are developed and manufactured observing of all relevant requirements with respect to environment protection Please observe local regulations for th...

Page 6: ...minals spring loaded 4 Push buttons for zero point and span point adjust ment 5 Status LED 6 Cable gland for wiring 1 Pressure connection nipples 2 DIP switches RS485 addressing 3 Terminals screw 4 Pu...

Page 7: ...erior of the EE610 front cover 0 0 0 0 0 0 0 0 1 1 0 0 0 0 0 0 1 0 1 0 Fig 4 DIP switches examples 4 1 1 Select the measurement range with S1 and S2 EE610 HV51A7 S1 S2 Pa mbar inch WC mm H2O 0 0 100 1...

Page 8: ...20 mA 3 2 mA 0 20 mA 1 mA Tab 6 Indication of p scale value low 5 of span Output signal p scale value high 5 of span 0 10 V 10 5 V 0 5 V 5 25 V 4 20 mA 20 8 mA 0 20 mA 21 mA Tab 7 Indication of p sca...

Page 9: ...mple Slave address is set via configuration software 0 0 0 1 1 0 0 0 0 0 0 1 0 1 0 Address setting via Dip Switch Setting the DIP switches to any other address than 0 overrules the default address 44...

Page 10: ...al pressure mm WC 10 4106 0x1009 Differential pressure mbar 100 4107 0x100A Differential pressure Pa 1 4108 0x100B Differential pressure kPa 1000 4109 0x100C Differential pressure inch WC 100 4110 0x1...

Page 11: ...allation Mount the EE610 onto a vertical smooth surface Important The pressure connection nipples must point downwards Avoid installation close to heaters and sources of strong electromagnetic interfe...

Page 12: ...pressure at the pressure connector Inverted connection leads to out of range information on the optional display and at the analogue outputs see 4 1 6 Outputs and 7 2 3 Out of range 6 Maintenance and...

Page 13: ...nd holding the zero point button for min 10 sec f The successful zero point adjustment is confirmed by the green LED turning on for 2 seconds 6 3 2 Span Point Adjustment The span point adjustment is u...

Page 14: ...failure of the attempt to adjust zero point or span point or to return to factory adjustment see 6 3 7 2 Display 7 2 1 Analogue version The display shows the measured differential pressure and the sel...

Page 15: ...sistor Measurement range 25 50 100 Pa 0 1 0 2 0 4 inch WC selectable with DIP switches1 0 100 Pa 0 0 4 inch WC WC water column Digital interface RS485 EE610 1 2 unit load Protocol Modbus RTU or BACnet...

Page 16: ...0 6460 Office Stuttgart Tel 49 151 538 37 500 E E Elektronik Italy info epluse it Tel 39 02 2707 86 36 E E Elektronik France info epluse fr Tel 33 4 74 72 35 82 E E Elektronik USA office epluse com Of...

Reviews: