Fig. 8
Dimension of pressure connection nipples
• Install first the pressure connection nipples (included in the scope of supply) onto the duct.
Use a Ø 7.5 mm drill.
• Connect the pressure hose (included in the scope of supply) first to the EE610 and then to the nipples
at the duct. Route the pressure hose for avoiding sharp bends which might lead to the hose
obstruction („Fig. 9 Pressure hose route“).
Fig. 9
Pressure hose route
Important: Make sure to connect the higher pressure at the “+” pressure connector and the lower
pressure at the “-“ pressure connector. Inverted connection leads to “out of range” information on the
optional display and at the analogue outputs, see „4.1.6 Outputs“ and „7.2.3 Out of range“.
6 Maintenance and service
EE610 does not require any special maintenance, nevertheless it is recommended to perform a zero
point adjustment every 12 month. If needed, the enclosure may be cleaned and the device may be
re-adjusted as described below.
6.1 Cleaning
Use a damp soft cloth to remove deposits of dust or dirt from the exterior of the device and from the
display. Do not attempt to clean the interior of the device. Do not use any solvents, alcohol or abrasive
cleaning agents.
6.2 Repairs
Repairs may be carried out by the manufacturer only. The attempt of unauthorised repair excludes any
warranty claims.