User Manual EE610 Low Differential Pressure Sensor
4.1.5 Select the output signal with S8
EE610 provides simultaneously a voltage and a current output signal at the spring terminals.
S8
Output signals
0
0-10 V and 4-20 mA
1
0-5 V and 0-20 mA
Tab. 5
DIP switch settings - Output signals
4.1.6 Outputs
The measured data is available at the spring terminals as 0-10 V and 4-20 mA or as 0-5 V
and 0-20 mA signals (see „4.1.5 Select the output signal with S8“).
Additionally, the analogue outputs indicate measurement out of range as follows.
If negative or positive differential pressure exceeds the span value of the selected measuring range by
5 % the analogue outputs indicate measurement out of range as follows.
Output signal
Δp < scale value low,
- 5 % of span
0-10 V
-0.5 V
0-5 V
-0.25 V
4-20 mA
3.2 mA
0-20 mA
-1 mA
Tab. 6
Indication of Δp < scale value low, - 5 % of span
Output signal
Δp > scale value high,
+ 5 % of span
0-10 V
10.5 V
0-5 V
5.25 V
4-20 mA
20.8 mA
0-20 mA
21 mA
Tab. 7
Indication of Δp > scale value high, + 5 % of span
4.2 Digital version
The EE610 is ready to use and does not require any configuration by the user. The factory setup of
EE610 corresponds to the type number ordered. For ordering guide please see data sheet at
www.epluse.com/ee610. If needed, the user can change the factory setup by using the USB configurati-
on adapter (code HA011066) and the EE-PCS, Product Configuration Software.
One can change the display visualisation (see chapter „7.2.2 Digital version“), the digital communication
parameters (see chapter „4.2.2 RS485 Digital Interface settings“) and the response time.
Note: The EE610 may not be connected to any additional power supply when using the USB configura-
tion adapter HA011066.
PC
HA011066
Service interface connector
Fig. 5