User Manual EE610 Low Differential Pressure Sensor
Response [Hex]: 2C 04 04 0A CC C2 01 55 C1
Modbus ID
address
Function
code
Byte
count
Register 1
value Hi
Register 1
value Lo
Register 2
value Hi
Register 2
value Lo
CRC
Response
[Hex]:
2C
04
04
0A
CC
C2
01
55
C1
For decoding of float values (stored according standard IEEE754), please refer to AN0103, chapter 7
(available on www.epluse.com/EE610).
Example of decoding
Response [Hex]
Value in decimal
Byte 1
(Register 2 - Hi)
Byte 2
(Register 2 – Lo)
Byte 3
(Register 1 - Hi)
Byte 4
(Register 1 - Lo)
C2
01
0A
CC
-32,260543
5 Installation
• Mount the EE610 onto a vertical, smooth surface.
• Important
:
The pressure connection nipples must point downwards.
• Avoid installation close to heaters and sources of strong electromagnetic interference.
• Insert the cable for supply voltage and output signal through the cable gland and connect it to the
spring terminals according to the wiring diagram („Fig. 3 Connection diagram“).
• Important: Make sure that the connecting cable or wires do not impact with the push buttons in order
to prevent unintentional trigger of the span or zero point adjustment.
• Close tightly the cable gland. This is essential for the compliance with the IP65 / NEMA4 protection
class of the EE610 enclosure.
Fig. 6
Mounting orientation
5.1 Pressure connection
Fig. 7
Pressure connection