User Manual EE610 Low Differential Pressure Sensor

3  Product Description

FOR CONDUIT

INSTALLATION

CABLE GLAND M16x1.5

90 

±0.3 

mm

3.54 

±0.11

46 mm

1.81“

5 mm

0.2“

80.6 mm

3.17“

5 mm

0.2“

Pressure fittings Ø 5mm

+ :  High pressure

-  :  Low pressure

Fig. 1 

Dimensions

Analogue version (A7)

Digital version (J3)

1

2

3

5

4

6

1

2

3

8

9

5

4

6

7

1.  Pressure connection nipples
2.  DIP switches: Configuration (Ranges, response 

time, ...)

3.  Terminals: spring loaded
4.  Push buttons for zero point and span point adjust-

ment

5.  Status LED
6.  Cable gland for wiring

1.  Pressure connection nipples
2.  DIP switches: RS485 addressing
3.  Terminals: screw
4.  Push buttons for zero point and span point adjust-

ment

5.  Status LED
6.  Slide switch termination resistor
7.  Service interface connector
8.  Cable gland for wiring
9.  Additional cable gland for daisy chain wiring

Fig. 2 

Design and components

Analogue version (A7)

Digital version (J3)

15...35 V DC

24 V AC ±20 % 

V+

GND

V+

A (=D+)

RS485

B (=D-)

GND

AV

1
2
3

1
2
3
4

+

-

~

~

+

-

~

~

V / mA

power supply

24 V AC ±20 %

15...35 V DC

Fig. 3 

Connection diagram

Summary of Contents for EE610

Page 1: ...BA_EE610_e v1 1 technical data are subject to change User Manual EE610 Low Differential Pressure Sensor...

Page 2: ...and found to comply with the limits for a Class A digital device pursuant to part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference when the...

Page 3: ...put signal with S8 8 4 1 6 Outputs 8 4 2 Digital version 8 4 2 1 EE PCS Product Configuration Software 9 4 2 2 RS485 Digital Interface settings 9 4 2 3 BACnet Protocol Settings 9 4 2 4 Modbus Protocol...

Page 4: ...E610 in explosive atmosphere or for measurement of aggressive gases Do not apply the nominal voltage to the output terminals 1 1 2 Mounting start up and operation The EE610 differential pressure senso...

Page 5: ...Environmental aspects Products from E E Elektronik are developed and manufactured observing of all relevant requirements with respect to environment protection Please observe local regulations for th...

Page 6: ...minals spring loaded 4 Push buttons for zero point and span point adjust ment 5 Status LED 6 Cable gland for wiring 1 Pressure connection nipples 2 DIP switches RS485 addressing 3 Terminals screw 4 Pu...

Page 7: ...erior of the EE610 front cover 0 0 0 0 0 0 0 0 1 1 0 0 0 0 0 0 1 0 1 0 Fig 4 DIP switches examples 4 1 1 Select the measurement range with S1 and S2 EE610 HV51A7 S1 S2 Pa mbar inch WC mm H2O 0 0 100 1...

Page 8: ...20 mA 3 2 mA 0 20 mA 1 mA Tab 6 Indication of p scale value low 5 of span Output signal p scale value high 5 of span 0 10 V 10 5 V 0 5 V 5 25 V 4 20 mA 20 8 mA 0 20 mA 21 mA Tab 7 Indication of p sca...

Page 9: ...mple Slave address is set via configuration software 0 0 0 1 1 0 0 0 0 0 0 1 0 1 0 Address setting via Dip Switch Setting the DIP switches to any other address than 0 overrules the default address 44...

Page 10: ...al pressure mm WC 10 4106 0x1009 Differential pressure mbar 100 4107 0x100A Differential pressure Pa 1 4108 0x100B Differential pressure kPa 1000 4109 0x100C Differential pressure inch WC 100 4110 0x1...

Page 11: ...allation Mount the EE610 onto a vertical smooth surface Important The pressure connection nipples must point downwards Avoid installation close to heaters and sources of strong electromagnetic interfe...

Page 12: ...pressure at the pressure connector Inverted connection leads to out of range information on the optional display and at the analogue outputs see 4 1 6 Outputs and 7 2 3 Out of range 6 Maintenance and...

Page 13: ...nd holding the zero point button for min 10 sec f The successful zero point adjustment is confirmed by the green LED turning on for 2 seconds 6 3 2 Span Point Adjustment The span point adjustment is u...

Page 14: ...failure of the attempt to adjust zero point or span point or to return to factory adjustment see 6 3 7 2 Display 7 2 1 Analogue version The display shows the measured differential pressure and the sel...

Page 15: ...sistor Measurement range 25 50 100 Pa 0 1 0 2 0 4 inch WC selectable with DIP switches1 0 100 Pa 0 0 4 inch WC WC water column Digital interface RS485 EE610 1 2 unit load Protocol Modbus RTU or BACnet...

Page 16: ...0 6460 Office Stuttgart Tel 49 151 538 37 500 E E Elektronik Italy info epluse it Tel 39 02 2707 86 36 E E Elektronik France info epluse fr Tel 33 4 74 72 35 82 E E Elektronik USA office epluse com Of...

Reviews: