Operating manual EE211 Heated humidity and temperature sensor
INTEGER 16 bit (read register):
Function code /
Register number
1)
[Dec]
Register address
2)
[Hex] Parameter name
Unit
3)
Scale
4)
30301
0x12C
temperature
[°C], [°F]
100
30302
0x12D
relative humidity
[%]
100
30303
0x12E
water vapour partial pressure
[mbar], [psi]
100
30304
0x12F
dew point temperature
[°C], [°F]
100
30305
0x130
wet bulb temperature
[°C], [°F]
100
30306
0x131
absolute humidity
[g/m³], [g/ft³]
100
30307
0x132
mixing ratio
[g/kg], [gr/lb]
100
30308
0x133
specific enthalpy
[kJ/kg], [BTU/lb]
100
30309
0x134
frost point temperature
[°C], [°F]
100
Tab. 4
Integer 16 bit (read register)
INTEGER 16 bit (read and write register):
Function code / Register number
1)
[Dec]
Register address
2)
[Hex] Parameter name
60001
0x00
Slave-ID
5)
modbus address
60002
0x01
Modbus protocol settings
6
Tab. 5
Integer 16 bit (read and write register)
INFO (read register):
Function code / Register number
1)
[Dec]
Register address
2)
[Hex] Parameter name
30001
0x00
Serial number (as ASCII)
30009
0x01
Firmware version
30010
0x09
Sensor Name
Tab. 6
Info (read register)
1)
Register number starts from 1
2)
Register address starts from 0
3)
The choice of measurement units (metric or non-metric) must be done in the ordering guide, see EE211 data sheet.
Switching from metric to non-metric or vice versa by using the EE-PCS is not possible.
4)
100 is scale 1:100 (2550 is equivalent to 25.5 °C)
5)
If the ID is set via DIP-switch the response will be NAK
6)
For Modbus protocol settings please see Application Note Modbus AN0103 (available on www.epluse.com/EE211)