Dynamic Fluid Measurement
SFC3 Liquid Pulse Manual
Quick Start
— 1-18
Date: 8/1/2019
RTD Wiring
When ‘Flow Computer’ is configured as 4 analog inputs and 2 RTD inputs, go to the wiring menu where it
says
RTD
and press <
ENTER>
. The flow computer shows wiring to RTD 1 and RTD 2. 100
platinum
can be used; a temperature range of -43
F to +300
F can be measured. RTD 1 is to the right where P5
designation is. In the figure below notice that each side of the RTD requires two wire connections. When
using less than 4 wires a jumper must be used to make up for the missing lead. Internal excitation current
source generated is approximately 7mA. .