Wiring Analog Output:
The analog outputs are located on the left side of P3 connector. Go to the wiring diagram and scroll down
to
Analog Output
and press <
ENTER>
. Wiring diagram shows typical Analog output wiring. Notice
that analog output will regulate 4-20mA current loop but DOES NOT source the power for it. External
power is required.
A
S S I G N I N G
/ R
A N G I N G T H E
4 - 2 0
M
A
A
N A L O G
O
U T P U T S
:
Go to the
I/O
assignment main menu and scroll to
Analog Output Assignment
. Press
<
ENTER>
. A selection menu is prompted. Select the analog output number and then enter what the 4mA
output will indicate and the 20mA. Make sure that the 20mA assignment value exceeds the upper range
limit of what you assigned the Analog output for, otherwise the analog output will not update beyond
20mA.