Dynamic Fluid Measurement
SFC3 Liquid Pulse Manual
Data Entry 2-5
Date: 8/1/2019
PORT
PC Communication Set Up
C o m m u n i c a t i o n P o r t N u m b e r ( 1 , 2 , 3 , 4 )
Enter the PC port used to communicate with the Flow Computer.
F l o w C o m p u t e r Po rt N u m b e r
There are two available ports in the Flow Computer. Port 1 is the RS-485 Modbus port. Port 2 is the RS-
232 Modbus port. The PC set up must match the Flow Computer port set up.
U n i t I D N u m b e r
The Unit ID Number is used strictly for communication purposes; it can take any value from 1 to 247. Only
one master can exist in each loop.
Note:
Do not duplicate the Unit ID number in a single communication loop!
This situation will lead to response collisions and inhibit communications
to units with duplicate ID numbers.
Mo d b u s T y p e
Note:
this parameter must be set the same for both the PC and the Flow
Computer for communication to occur.
The Modbus Communication Specification is either Binary RTU or ASCII.
P a r i t y
Note:
this parameter must be set the same for both the PC and the Flow
Computer for communication to occur.
RTU - NONE
ASCII - EVEN or ODD
Set the parity to match the
Modbus Type
.
B a u d R a t e
Note: this parameter must be set the same for both the PC and the
Flow Computer for communication to occur.
Summary of Contents for SFC3
Page 17: ...Dynamic Fluid Measurement SFC3 Liquid Pulse Manual Quick Start 1 12 Date 8 1 2019 ...
Page 18: ...Dynamic Fluid Measurement SFC3 Liquid Pulse Manual Quick Start 1 13 Date 8 1 2019 ...
Page 35: ...Dynamic Fluid Measurement SFC3 Liquid Pulse Manual Quick Start 1 30 Date 8 1 2019 ...
Page 88: ...Dynamic Fluid Measurement SFC3 Liquid Pulse Manual Flow Equations 3 5 Date 8 1 2019 ...