QUICK START – STEP 5
BASIC SETTINGS SUB-MENU
Step 5a
U
se the “DOWN” button and ”OK” button to select the “BASIC SETTINGS” sub-menu
from the “ADMIN MENU”. Verify that all the “BASIC SETTINGS” are correct or as
desired for your system, especially the valve
MODEL
(see next page)
.
1. Period:
The rolling time period over which the unit calculates the
percentage
on-time
and %
deviation
for each outlet. In this example, data within
the last 4 days will be used in the calculation. Alarms are checked at
1/5th this period. Default value is 30 days.
2. Error %:
The maximum allowable percent deviation from equal distribution for all
outlets. Ideally an equal amount of time is spent on each outlet. The
error % control allows an adjustment of when an error should be
signalled. In the above example, a 4 outlet valve should spend 25% of
the time on each outlet, so the 10% allowable deviation means that the
value for each outlet must fall between 15% and 35%. Anything outside
of this range results in a “percent deviation exceeded” (PCT DEV) error
condition.
Select “SAVE” then “OK” , after making any changes.
*saved* will appear briefly on the screen to confirm your changes are saved.
Oct 2020 IVM6000-LP
TM
Quick Start Guide Page 5
04 days 00H
10%
LOW
6606
OK
PERIOD
ERROR%
SENSITIVITY
MODEL
SAVE
BASIC SETTINGS
Keypad functions
UP/DOWN: Change value/menu item
OK:
Confirm value/Select menu item
PAGE:
Go to next screen
1. Period
2. Error %