Table 2: IVM6000 Reference table of alarm
sensitivity level settings.
Number of times event has to occur for
alarm to be triggered
Event Code
Event Name
Low
Medium
High
0
EVENT_NO_EVENT
0
0
0
1
EVENT_TEST
1
1
1
2
EVENT_OUTLET_NO_INLET
254
1
1
3
EVENT_OUTLET_ON_TOO_LONG
254
1
1
4
EVENT_OUTLET_OFF_TOO_SOON
0
16
1
5
EVENT_TOO_MANY_OUTLETS
254
1
1
6
EVENT_INLET_NO_OUTLET
0
0
1
7
EVENT_OUT_OF_ORDER
254
8
1
8
EVENT_PCT_DEVIATION
1
1
1
9
EVENT_RESET
0
0
1
10
ETC INTERNAL USE
-
-
-
11
EVENT_OUTLET_STUCK
254
16
1
12
EVENT_VOLTAGE_LOW
1
1
1
13
EVENT_VOLTAGE_OK
0
0
1
14
EVENT_INAPPROPRIATE_OUTLET
1
1
1
15
ETC INTERNAL USE
-
-
-
16
EVENT_RTC_BATTERY_LOW
1
1
1
17
EVENT_RTC_OSCF
1
1
1
18
EVENT_CNT_CLEAR
0
0
1
19
EVENT_THERMO_WARN
254
16
1
20
EVENT_THERMO_ALARM
1
1
1
*Note: “0” value means that the event will never trigger and alarm at that sensitivity level.
Oct 2020 IVM6000-LP
TM
Quick Start Guide Page 21