APPENDIX
PROMATRIX System User Handbook 1.1
6-1
6.
Appendix
6.1
PROMATRIX Hardware Configuration
6.1.1 DCS 400
When configuring and initially operating the DCS 400 system, please proceed as follows:
1. Cabling
è
Use the supplied flat-wire cable for connecting the relay modules DCS 408, DCS 409 in the desired order to
the control module DCS 401. Mixed installation of relay modules is possible; numbering the relays is type-
specific and has to be performed according to their sequence.
example:
Sequence
Module
Line relay No.
Control relay No.
1
DCS 408
1 - 5
2
DCS 408
6 - 10
3
DCS 409
1 - 5
4
DCS 408
11 - 15
5
DCS 409
6 - 10
6
DCS 408
16 - 20
...
...
...
...
è
Use the supplied flat-wire cable for connecting the logic input module DCS 412 to the control module DCS
401. Numbering the logic inputs has to be performed according to their sequence.
example:
Sequence
Module
Logic input No.
1
DCS 412
1 - 12
2
DCS 412
13 - 24
3
DCS 412
25 - 36
...
...
...
è
Use the supplied flat-wire cable for connecting the analog input / output modules DCS 416 to the control
module DCS 401. Numbering the analog inputs and outputs has to be performed according to their sequence.
example:
Sequence
Module
Analog input No.
Analog output No.
1
DCS 416
1 - 8
1 - 8
2
DCS 416
9 - 16
9 - 16
è
Connect the control module DCS 401 via RJ-45 cable to the REMOTE CONTROL socket on the DPM 4000.