9.3 Input and Output of ITVC
This paragraph lists the inputs and outputs available in the ITVC electronics. These I/O’s are collected in two terminal
blocks, one terminal block is available to user, for connection of signals with the control room, the other one is available
for connection of the actuator signals (Solenoid operated Valves, transmitters, etc.). The electrical features of the I/O’s
are described in the
INSTALLATION
chapter
I/O’s available on
user
terminal block
Digital inputs:
o
2 configurable digital inputs (IN3, IN4) + Open and Close remote controls, optocoupled, 1 common.
o
2 independent, separated ESD inputs (ESD1,ESD2), optocoupled,
o
2 configurable digital inputs (IN1,IN2), optocoupled, 1 common
Outputs relays:
o
1 Monitor relay, single side stable, SPDT contact, voltage free (Monitor Relay)
o
4 configurable, latched, SPST contact, voltage free (R1,R2, R3, R4)
Analogue input:
o
1 x 4-20mA channels, optocoupled isolated amplifier, factory configurable
Analogue output:
o
2 x 4-20mA channels, optocoupled isolated amplifier, active and passive current loop, factory configurable
I/O’s available on the
actuator
terminal block
Digital inputs:
o
4 digital inputs , optocoupled, 1 common, factory configurable
Digital outputs:
o
8 x digital outputs , 1 common, fuse protected, to drive Solenoid Operated Valves, factory configurable
Outputs relays:
o
3 x latched, SPST contact, voltage free, factory configurable
Analogue input:
o
4 x 4-20mA channels, optocoupled isolated amplifier, factory configurable
9.4 Status signalling
Output status of system ITVC-H/PCU-Actuator is available:
Locally, by the HMI, Human Machine Interface, described in the chapter ITVC HMI
remotely by
o
1 Monitor relay: it summarizes the Alarm and MRT alarm status
o
4 latched, output relays. The condition to switch of each relay can be set by the configuration options
9.5 BUS control
2 independent RS 485, Modbus RTU communication lines, are available to control the ITVC by a Modbus
master station.