9.2 Main characteristics
Here below are listed the most important functions of the BASIC ITVC.
Control and drive of DVG Automation pneumatic and hydraulic actuators, single acting spring return and
double acting, on-off service
Failsafe function
Redundant ESD E
mergency
S
hut-
D
own function (ESD1 and ESD2 channels with diagnostic each channel)
Output to control
S
olenoid
O
perated
V
alves (
SOV
), fuse protection in each output
Test of coils of
S
olenoid
O
perated
V
alves (
SOV
)
Standard digital hardwired remote control
Interlock controls
Redundant Modbus RTU communication line
Local actuator control
Human Machine Interface
(
HMI
) with graphic LCD display and non-intrusive, touch-sensitive, pushbuttons
Multi-language menu,
icon
based
User friendly
navigation in the menu
Local configuration
Diagnostic functions
Two microcontrollers
working in parallel with cross comparison of operations and diagnostic
Access to menu by password to protect against unauthorized change
Bluetooth wireless communication
Sensor of Temperature of Electronics
Alarm, Warning, Event logger
Real time clock and battery
SIL 3 compliance
for the SIF functions (ESD Emergency Shut-Down, Line Break and Panic Button)
1oo1, 1oo2, 2oo3 and 1oo3
configuration of analogue input channels with diagnostic
Operating temperature and enclosure suitable for application in field, according to limits reported in the
Classification/Certification paragraph
Separated mounting option
Here below are listed the most important functions available and activated by DVG Automation according to the user
request
PST
function (
P
artial
S
troke
T
est)
(see Annex A: PST function)
Line Break
(
LB
and
LB-d
) function
(see Annex B: Line Break function)
HPU
(
H
ydraulic
P
ower
U
nit) control module
(see Annex C: HPU control module)
HIPPS
(
H
igh
I
ntegrity
P
ressure
P
rotection
S
ystem) function
(see Annex D: HIPPS function)
Panic Button (PB)
(see Optional panic button paragraph)
Optional battery
(see Optional battery paragraph or Annex B)
Separated mounting option
: it allows mounting the ITVC separately from actuator. It is especially useful when the
actuator has to be mounted in a difficult access position, or highly vibrating valve or in excessive high/low temperature
area. The maximum length of cable between ITVC and actuator is
50m
.
SIL features:
the specific ITVC SIF functions “
ESD Emergency shutdown
”,
Line Break
and
Panic Button
comply
with
IEC61508,
application
“Low Demand mode”.
The certificate 43SO00071 is available on request.
Optional battery
: if required, ITVC can be equipped (only -20°÷+85°C ITVC version) with a rechargeable lithium-ion
battery, which in case of power supply failure, keeps the ITVC functional, in monitoring mode. The battery is located