Nº 5. S/3-2 detectors connection to Eurosondelco
19. GENERAL CONSIDERATIONS
EURODETECTORS O
2
These detectors operate differently from the others: the Alarm Level is upwards -more oxygen- and the Ventilation Level is
downwards -less oxygen-.
2 SPEED VENTILATIONS
A non-programmable general delay retards 15 s the switch from the connection between the 1st and 2nd speed ventilation.
Furthermore, it will retard the switch of disconnection from the 2nd to 1st speed in order to prevent faults in the ventilation
engines.
AUTOMATIC BATTERY FAULT OPERATION
In the event of a power fault 220V AC an acoustic will go off and the display lights in the module lines will switch off to
reduce consumption.
If the fault lasts for a long time, when the battery voltage reaches 9V another acoustic will go off.
If the power fault continues to last, when 8V are reached the module lines will automatically be disconnected: OFF position.
When the power fault is fixed the module lines will automatically be connected with the parameters they had beforehand.
PROTECTING THE DETECTOR POWER SUPPLY IN THE MODULE LINES
The voltage output to supply the detectors in the module lines incorporates a protection fuse that is automatically replaced.
This fuse opens up automatically whenever there is a short circuit on the line or the consumption increases (>1A). Its
replacement will be automatic and retarded when the anomaly causing its behaviour disappears.
Engli
sh
Summary of Contents for EUROSONDELCO
Page 1: ......
Page 2: ......
Page 4: ...28 2005 DURAN ELECTRONICA S L All rights reserved www duranelectronica com 28...
Page 15: ...X maneuro INS v02 39 English QUICK PROGRAMMING...
Page 21: ...45 English X maneuro INS v02 QUICK PROGRAMMING...
Page 24: ...48 2005 DURAN ELECTRONICA S L All rights reserved www duranelectronica com QUICK PROGRAMMING...
Page 37: ...X maneuro INS v02 61...
Page 38: ...62 2005 DURAN ELECTRONICA S L All rights reserved www duranelectronica com 62...
Page 40: ...64 2005 DURAN ELECTRONICA S L All rights reserved www duranelectronica com 64...
Page 51: ...X maneuro INS v02 75 PROGRAMA O RAPIDA Portugu s...
Page 58: ...82 2005 DURAN ELECTRONICA S L All rights reserved www duranelectronica com 82...
Page 60: ...84 2005 DURAN ELECTRONICA S L All rights reserved www duranelectronica com 84...
Page 71: ...X maneuro INS v02 95 PROGRAMMATION R PIDE Fran ais...
Page 78: ...102 2005 DURAN ELECTRONICA S L All rights reserved www duranelectronica com 102...
Page 89: ...113 X maneuro INS v01 English PROGRAMMATION RAPIDE...
Page 93: ...117 X maneuro INS v01 English SCHNELLPROGRAMMIERUNG 2 L ftungsstufen optionen...
Page 94: ...118 2004 DURAN ELECTRONICA S L All rights reserved www duranelectronica com...
Page 95: ......