X-maneuro-INS-v02
43
Engli
sh
7. CO DETECTION, ITALIAN STANDARD. Default configuration
If you do not need to change any of the parameters described, it will not be necessary to enter the SYSTEM PROGRAMMING
menu.
If you need to change any of the parameters, go directly to that parameter by pressing
FORWARD
.
1, 2 or 4 VENTILATION GROUPS
Ventilation:
ON:
If 2 detectors are at 50 ppm -1 minute input retard-
ON:
1 100-ppm detector -with 1 minute input retard-
OFF:
whenever one of the ON conditions is not met -2 minutes output
retard-
Alarm:
ON
200 ppm -3 minutes input retard-
Number of groups:
1
Cyclical ventilation:
Each “0” hours
Cyclical ventilation activation time:
5 minutes
Overhauls Interval:
Each “0” months
Engineer code:
66666 -5 times
ENTER
-
PROGRAMMING THE SYSTEM
With the Module line in OFF position:
1. Press
PROGRAMMING
.
“
Insert Code
” is displayed. Insert the Engineer Code -default setting: 66666. Press
ENTER
5 times-.
NUMBER OF GROUPS
Number of Groups is displayed -default setting: 1-
2. Press
FORWARD
to select the number of groups: 1, 2 or 4 groups.
3. Press
ENTER
to memorise.
SETTING THE GROUPS
4. Press
PROGRAMMING
to set the groups.
“
Group 1
” is displayed.
5. Press
FORWARD
to select the other groups.
6. Press
PROGRAMMING.
Type of gas is displayed -default setting: CO-.
7. Press
PROGRAMMING
to select other gases.
8. Press
FORWARD
to select the type of gas -CO, H
2
S, SO
2
, NO, NO
2
, Cl
2
, HCl, 0
2
, EXP-.
9. Press
ENTER
to memorise.
Alarm level Group 1 is displayed -default setting: 200 ppm-.
10. Press
PROGRAMMING
to change to other levels.
11. Press
FORWARD
to select the alarm level.
Summary of Contents for EUROSONDELCO
Page 1: ......
Page 2: ......
Page 4: ...28 2005 DURAN ELECTRONICA S L All rights reserved www duranelectronica com 28...
Page 15: ...X maneuro INS v02 39 English QUICK PROGRAMMING...
Page 21: ...45 English X maneuro INS v02 QUICK PROGRAMMING...
Page 24: ...48 2005 DURAN ELECTRONICA S L All rights reserved www duranelectronica com QUICK PROGRAMMING...
Page 37: ...X maneuro INS v02 61...
Page 38: ...62 2005 DURAN ELECTRONICA S L All rights reserved www duranelectronica com 62...
Page 40: ...64 2005 DURAN ELECTRONICA S L All rights reserved www duranelectronica com 64...
Page 51: ...X maneuro INS v02 75 PROGRAMA O RAPIDA Portugu s...
Page 58: ...82 2005 DURAN ELECTRONICA S L All rights reserved www duranelectronica com 82...
Page 60: ...84 2005 DURAN ELECTRONICA S L All rights reserved www duranelectronica com 84...
Page 71: ...X maneuro INS v02 95 PROGRAMMATION R PIDE Fran ais...
Page 78: ...102 2005 DURAN ELECTRONICA S L All rights reserved www duranelectronica com 102...
Page 89: ...113 X maneuro INS v01 English PROGRAMMATION RAPIDE...
Page 93: ...117 X maneuro INS v01 English SCHNELLPROGRAMMIERUNG 2 L ftungsstufen optionen...
Page 94: ...118 2004 DURAN ELECTRONICA S L All rights reserved www duranelectronica com...
Page 95: ......