Adjusting the Flame Monitor
Safety time
Switches S3 and S4
Switch position
DIP position*
1
2
1s
off
off
2s
on
off
3s
off
on
5s
on
on
*
DIP positions 1 and 2 must be set in accordance with the safety
time noted on the type plate!
Table 6.2: Setting MODE switches S3 and S4
To avoid an error shutdown, MODE switches S3 and S4 must be set to the
same position within 8s.
D
−
LX 200, D
−
LX 720
65