Modbus
(8E1) 1 start bit, 8 data bits, Even-Parity and 1 stop bit
with data transfer rates 9600bps and 19200bps.
The address is set according to the following table:
Switch position
Description
Switch position
Modbus slave address
Current
output
DIP position*
1
2
3
4
5
6
7*
8
0…20mA
on
4…20mA
off
reserved*
Modbus ADDR
1**
on
on
on
on
on
on
Modbus ADDR 2
off
on
on
on
on
on
Modbus ADDR 3
on
off
on
on
on
on
Modbus ADDR 4
off
off
on
on
on
on
Modbus ADDR 5
on
on
off
on
on
on
Modbus ADDR 6
off
on
off
on
on
on
…
Modbus ADDR 9
on
on
on
off
on
on
…
Modbus ADDR 64
off
off
off
off
off
off
*
DIP position 7 is reserved!
**
Presetting
at delivery
Table 8.2: Setting for MODE switch S5
The current output range noted on the type plate must match the range set on
the device!
8.3 Modbus
Slave Address FunctionCode
Data
CRC
1 byte
1 byte
0 up to 252 byte(s)
2 bytes
CRC Low, CRC Hi
Table 8.3: Modbus RTU Message Frame
0
from 1 to 247
from 248 to 255
Broadcast address Slave individual addresses
Reserved
Table 8.4: Modbus Slave Address Range
D
−
LX 200, D
−
LX 720
85
Summary of Contents for D-LX 200
Page 1: ...D LX 200 D LX 720 Compact Flame Monitor GmbH Kollaustra e 105 22453 Hamburg www durag de...
Page 8: ......
Page 10: ......
Page 14: ......
Page 16: ......
Page 22: ......
Page 24: ......
Page 32: ......
Page 42: ......
Page 52: ......
Page 66: ......
Page 68: ......
Page 80: ......
Page 82: ......
Page 92: ......
Page 94: ......
Page 100: ......
Page 106: ......
Page 108: ...Declaration of conformity 108 D LX 200 D LX 720...
Page 114: ......
Page 116: ...GmbH Kollaustra e 105 22453 Hamburg www durag de...