Duracomm | 17
Default Analog Alarm Settings
The default alarm setting is shown in the table below. The alarm triggers when the voltage/ampere level falls below the
“Under Alarm Threshold” setting or rise above the “Over Alarm Threshold” setting. If auto recover is enabled, the alarm
recovers when the voltage/ampere level rise above the “Under Alarm Recovery” setting or falls below the “Over Alarm
Recovery” setting.
PSRM-4012NFPMU
Measurement
Under Alarm
Threshold
Under Alarm
Recovery
Over Alarm
Threshold
Over Alarm
Recovery
Display Range
AC Line, Volts
100
105
140
135
-15 / 150
Amps Power Supply
-5
0
90
85
-10 / 100
Amps Battery
-5
0
90
85
-10 / 100
Volt Power Supply
10.5
12.0
15.5
14.5
-7 / 70
Volt Battery Charger Fail
13.3
13.6
15.0
14.0
-7 / 70
Volt Battery Battery Low
11.5
12.5
15.0
14.0
-7 / 70
Volt Battery Battery Fail
10.0
12.5
15.0
14.0
-7 / 70
PSRM-2524NFPMU
Measurement
Under Alarm
Threshold
Under Alarm
Recovery
Over Alarm
Threshold
Over Alarm
Recovery
Display Range
AC Line, Volts
100
105
140
135
-15 / 150
Amps Power Supply
-5
0
90
85
-10 / 100
Amps Battery
-5
0
90
85
-10 / 100
Volt Power Supply
21
25
30
29
-7 / 70
Volt Battery Charger Fail
26.3
26.9
29
28
-7 / 70
Volt Battery Battery Low
23.0
25.0
29
28
-7 / 70
Volt Battery Battery Fail
20.0
25.0
29
28
-7 / 70
PSRM-1048NFPMU
Measurement
Under Alarm
Threshold
Under Alarm
Recovery
Over Alarm
Threshold
Over Alarm
Recovery
Display Range
AC Line, Volts
100
105
140
135
-15 / 150
Amps Power Supply
-5
0
90
85
-10 / 100
Amps Battery
-5
0
90
85
-10 / 100
Volt Power Supply
42
46
60
58
-7 / 70
Volt Battery Charger Fail
51.8
52.4
58
56
-7 / 70
Volt Battery Battery Low
46.0
50.0
58
56
-7 / 70
Volt Battery Battery Fail
40.0
50.0
58
56
-7 / 70