DuraComm PSRM-1248NFPMU Owner'S Manual Download Page 16

Duracomm | 16 

Alarm Setup Page 

In the monitoring unit, the analog alarms can be set by selecting the drop-down menu next to the “Analogs” label. As 
shown in the figure, the “AC Line” is currently selected. 

The Digital Output 1 controls the ON/OFF state of the Power Supply. The user must be logged in as the admin or control 
user to adjust the digital outputs. The digital outputs can be controlled by the buttons on the status page, mobile page, 
or via SNMP on the unit. Optionally, they can be automatically controlled by connecting them to an alarm on the 
“Alarms” screen. 

The Alarm Setup page is where thresholds are set to define alarm conditions for the analog channels. You can choose to 
set an email notification when the alarm conditions are met. 

The “Log All Alarms” setting in the “Global Settings” on this page is the same as the “Log Alarms” setting on the Device 
Setup page. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 12. Alarm Setup Page.

 

Summary of Contents for PSRM-1248NFPMU

Page 1: ...OG 2021 03 30 www duracomm com RACK MOUNT POWER SUPPLY WITH BATTERY MANAGEMENT SYSTEM NFPA 1221 ALARMS MONITORING CONTROL PSRM 5012NFPMU PSRM 2524NFPMU PSRM 1248NFPMU OWNER S GUIDE 2020 Duracomm Corpo...

Page 2: ...cators 6 Front Panel Display 6 Rear Panel Connections 6 Rear Alarm Wiring 7 Battery LVD 7 Battery Charging 7 Section 3 Remote Monitoring 8 Connecting to the Remote Monitoring Unit via the Internet 8 U...

Page 3: ...e proper AC input voltage on the voltage selector Excessive input voltage may cause damage to the internal circuit 7 Ensure DC polarities and rated voltage are correct for the load and battery connect...

Page 4: ...can access the setup screens and change the control settings by logging into the RMCU via the browser Alarm conditions are configurable including the over under thresholds Alarm notifications can be...

Page 5: ...ode before making battery connection or disconnection Conductor Pretreatment All kinds of copper conductors can be clamped without treatment DO NOT solder tin stranded conductors The solder yields and...

Page 6: ...he currently selected output ON and OFF Rear Panel Connections Due to safety use only type SPT 2 cord or heavier duty cord Use proper size AWG copper wires for load and battery terminals Only connect...

Page 7: ...reconnect voltage Battery Charging ONLY charge lead acid AGM batteries Other types of batteries may burst causing personal injury and damage Figure below shows the charging curve of lead acid AGM batt...

Page 8: ...omm MAC addresses all start with a base address of 70 B3 D5 6B 3 Write down the IP address of the unit then proceed to the section in this manual named Open a Web Connection to the Unit Using Static I...

Page 9: ...he screenshot below If you are unable to connect to the device with the browser you will need to use a terminal with a USB connection to access the device and configure the IP address If the unit resp...

Page 10: ...luding the calibration setting to accurately read the voltage and the current will be lost Re calibration of the unit at the factory will be required Network Reset To reset network settings press the...

Page 11: ...monitoring unit Factory default username and password are as follows Admin users have full user control of the device Username admin Password admin Control users have limited control capability access...

Page 12: ...ng SNMP traps you can search for training material online under SNMP Traps MIB Browsers and SNMP Monitoring The MIB file for the unit can be downloaded after you connect to it with your browser Go to...

Page 13: ...Messages To send a text you need to send an email to the appropriate email address of your cell phone carrier Simply enter your phone number with no spaces parenthesis or hyphens followed by your carr...

Page 14: ...nload all log files before deleting the The ability to log readings when an alarm occurs is also included To turn off periodic logging enter 0 as the logging rate You can set up logging to occur only...

Page 15: ...he name fields on the left are left blank the channel will be hidden on the status page Inputs and outputs of the monitor unit are shown on the Sensor Setup page The user can enter text to change the...

Page 16: ...puts The digital outputs can be controlled by the buttons on the status page mobile page or via SNMP on the unit Optionally they can be automatically controlled by connecting them to an alarm on the A...

Page 17: ...14 0 7 70 Volt Battery Battery Low 11 5 12 5 15 0 14 0 7 70 Volt Battery Battery Fail 10 0 12 5 15 0 14 0 7 70 PSRM 2524NFPMU Measurement Under Alarm Threshold Under Alarm Recovery Over Alarm Thresho...

Page 18: ...tatus Page This page shows the status of all analog and digital inputs User may also download the Log File from this page AC voltage and output current of individual channels are approximated Figure 1...

Page 19: ...C 10 C Shutdown output voltage auto recover Battery Charger Output Charger Voltage 13 8 VDC 27 6 VDC 55 2 VDC Charger Current 7 Amps 4 Amps 2 Amps Charger Module Power 100 Watts 120 Watts 120 Watts Su...

Page 20: ...ny product needing in or out of warranty service to be returned to DuraComm All requests for warranty service must be accompanied by proof of purchase such as a bill of sale with purchase date identif...

Reviews: