INSTALLATION BLOCK DIAGRAM
HE1U-5012-BC-MU Alarm Connector
B5V and Alarm In
Output Status
Switch Closed
Alarm Closed
Switch Open
Alarm Open
Between G and Alarm Out
Output Status
Open-Drain
500 mA max, 60 V max
Alarm ON/LOW
Shorted
Alarm OFF/HIGH
Open
HE1U-5012-BC-MU Wiring Layout
This system setup will provide continuous power to the load and maintain the battery bank with a float charge circuit while AC
power is on. There is a seamless transfer of the load to the battery when the AC power goes off. The LVD will disconnect the battery if
the voltage drops below 10.5 VDC. The battery reconnects once AC power is restored and voltage reaches 12.5 VDC.