DuraComm HE1U-5012-BC-MU Product User Manual Download Page 4

   

4

   of   23   

August   3,   2016

 

 

INSTALLATION BLOCK DIAGRAM 
 

   

 
HE1U-5012-BC-MU Alarm Connector 
 
B5V and Alarm In 

Output Status 

Switch Closed 

Alarm Closed 

Switch Open 

Alarm Open 

 
 
Between G and Alarm Out 

Output Status 

Open-Drain 

500 mA max, 60 V max

 

Alarm ON/LOW 

Shorted 

Alarm OFF/HIGH 

Open 

 

 

HE1U-5012-BC-MU Wiring Layout 
 

This system setup will provide continuous power to the load and maintain the battery bank with a float charge circuit while AC 

power is on. There is a seamless transfer of the load to the battery when the AC power goes off. The LVD will disconnect the battery if 
the voltage drops below 10.5 VDC. The battery reconnects once AC power is restored and voltage reaches 12.5 VDC.

 

 
 
 
 
 

 

 
 
 
 
 
 
 
 
 
 
 
 
 

 

Summary of Contents for HE1U-5012-BC-MU

Page 1: ...ply ON OFF remote control and DC OK The HE1U 5012 BC MU comes with a 3 year warranty The new internal Remote Monitoring and Control Unit RMCU provides the ability to remotely monitor the AC voltage po...

Page 2: ...19 W x 14 D Weight 9 1 lbs RMCU SPECIFICATIONS Hardware Revision 2 0 Firmware Revision 2 7 Network Connector RJ 45 10 100 Ethernet with activity LEDs Backup Battery CR2032 Memory Card 4GB Micro SD Vol...

Page 3: ...isconnect voltage INSTALLER NOTES NOTE DO NOT block any of the cooling vents on the sides and top and always allow adequate ventilation by not installing the unit inside tightly closed spaces Physical...

Page 4: ...arm ON LOW Shorted Alarm OFF HIGH Open HE1U 5012 BC MU Wiring Layout This system setup will provide continuous power to the load and maintain the battery bank with a float charge circuit while AC powe...

Page 5: ...5 of 23 August 3 2016...

Page 6: ...ress of 70 B3 D5 6B 3 Write down the IP address of the HE1U 5012 BC MU then proceed to the section in this manual named Open a Web Connection to the HE1U 5012 BC MU Using Static HE1U 5012 BC MU IP and...

Page 7: ...fox internet Explorer etc and enter the IP address of the power supply on your network into the URL box on the browser see the screenshot below If you are unable to connect to the device with the brow...

Page 8: ...Login Enter the user name and password Factory default username and password are as follows Admin Users have full control of the device Username admin cannot be changed Password admin Control users ha...

Page 9: ...9 of 23 August 3 2016 NETWORK SETUP...

Page 10: ...SNMP traps you can search for training material online under SNMP Traps MIB Browsers and SNMP Monitoring The MIB file for the HE1U 5012 BC MU can be downloaded from the HE1U 5012 BC MU after you conn...

Page 11: ...ail Setup Enter the required email setup parameters given to you by your System Administrator You can also send a test email from this screen Firmware 2 7 adds the ability to configure a periodic stat...

Page 12: ...12 of 23 August 3 2016 DEVICE SETUP...

Page 13: ...e file size reaches 5MB Download all log files before deleting them With REV 2 3 Firmware the ability to log readings when an alarm occurs has been added To turn off periodic logging just enter 0 as t...

Page 14: ...14 of 23 August 3 2016 SENSOR SETUP...

Page 15: ...ee the Alarm Setup section for more information In the HE1U 5012 BC MU the Digital Output 1 is an alarm output and Digital Output 2 controls the ON OFF state of the power supply The user must be logge...

Page 16: ...16 of 23 August 3 2016 ALARM SETUP...

Page 17: ...17 of 23 August 3 2016...

Page 18: ...added the ability to log alarms The Log Alarms setting on the Device Setup Page is the same as the Global Settings Log All Alarms setting on this page Digital output alarm conditions can be set to Nev...

Page 19: ...be taken when changing any of these settings NOTE To hard reset your device back to factory settings press the red button on the HE1U 5012 BC MU PCB and hold it for more than 30 seconds You will need...

Page 20: ...August 3 2016 REMOTE MONITORING AND CONTROL STATUS PAGE Status screen This screen shows the status of all analog and digital inputs A user can also download the Log file from this page AC Voltage is a...

Page 21: ...devices Just use the same IP address and add m for example 192 168 100 220 m HE1U 5012 BC MU MAINTENANCE Battery The battery on the HE1U 5012 BC MU is used to back up the real time clock for logging p...

Page 22: ...Copper ferrules prevent the current transfer from being influenced by dissimilar metals and remove the risk of corrosion Always use the correct tool to crimp the ferrule RECOMMENDED COPPER WIRE SIZE F...

Page 23: ...prior to inclusion of such changes DuraComm requires any product needing in or out of warranty service to be returned to DuraComm All requests for warranty service must be accompanied by proof of pur...