Output Voltage........................................................................................................................................................................ 13.8 VDC 
Output Voltage Tolerance............................................................................................................................................................+/- 1 % 
Output Amperage ............................................................................................................................................................ 50 Amps max. 
Maximum Power, continuous .................................................................................................................................................750 Watts 
Maximum Ripple and Noise..........................................................................................................................................150 mV p-p max 
Input Voltage, Switch Selectable .................................................................................................................................. 110-or 220 VAC 
Input Frequency Range ........................................................................................................................................................... 47-63 Hz 
Maximum AC Current ..............................................................................................................8.2 Amps/115 VAC; 3.9 Amps/230 VAC 
Typical Efficiency............................................................................................................................................................................89 % 
Max Inrush Current, single cycle ............................................................................................25 Amps / 115 VAC, 40 Amps / 230VAC 
Short Circuit Protection.................................................................................................................................. Constant Current Limiting 
Overload Protection (operates) ................................................................................................................................. typical 105-125 % 
Line Regulation.........................................................................................................................................................................+/- 0.5 % 
Load Regulation .......................................................................................................................................................................+/- 0.5 % 
Fan Control.................................................................................................................................... Heat sink temp >140 F (60 C) = ON 
Over Temperature ........................................................................................................................ >195 F (90 C) auto output shutdown 
Rise Time following ON ................................................................................................................................................................50 mS 
Hold Time following OFF ..............................................................................................................................................................10 mS 
Working Temperature Range ............................................................................................................. -22 F to +158 F (-30 C to +70 C)  
Storage Temperature ......................................................................................................................... -40 F to +185 F (-40 C to +85 C) 
Withstand Voltage ..................3 KVAC @ 10 ma (I/P-O/P)/1 min, 2 KVAC @ 10 ma (I/P-FG)/1 min, 500 V @ 10 ma (O/P-FG)/1 min 
Dimensions....................................................................................................................................................... 1.75” H x 19” W x 14” D 
Weight ......................................................................................................................................................................................... 9.1 lbs 

 
RMCU SPECIFICATIONS 

 

Hardware Revision ............................................................................................................................................................................ 2.0 
Firmware Revision............................................................................................................................................................................. 2.7 
Network Connector............................................................................................................. RJ-45 (10/100 Ethernet) with activity LEDs 
Backup Battery ..........................................................................................................................................................................CR2032 
Memory Card................................................................................................................................................................... 4GB Micro SD 
Voltage Measurement Range...................................................................................................................................0 VDC to 100 VDC 
Current Measurement Range ................................................................................................................................0 Amps to 100 Amps 
Digital Alarm input ........................................................................................................................................ Normally Closed Contacts  
Alarm Output ...................................................................... Open Collector, 60 VDC Max (REV 2 RMU Hardware), 500 mA sink Max 
Alarm Response Time ................................................................................................................................................................. 250ms 
Alarm Notifications.................................................................................................................................................. Email and/or SNMP 
Logging Rate .............................................................................................................................1 minute resolution, 1 minute to 1 hour 
Log Download Format ............................................................................................................... .Comma Separated Values (CSV) File 
SNMP MIB File ............................................................................................................................... Download from Device Setup Page 
5V Supply Maximum Current...............................................................................................................................................300 mAmps 

BATTERY BACK UP & CHARGER  

Maximum Power, continuous .................................................................................................................................................750 Watts 
Auto-revert to battery or power supply ..................................................................Provided by dual Shottky diode in OR configuration 
Maximum output current in battery mode ........................................................................................75 amps (limited by Shottky diode) 
Maximum charge voltage ....................................................................................................................................................... 13.8 VDC 
Maximum recharge rate................................................................................................................................................................ 2 amp  

 

Note: 

The battery charger is a fixed resistance type that provides a tapering current output.  A float charge current of 1-2 amps will 

be maintained after the battery is charged. 

 

 

Summary of Contents for HE1U-5012-BC-MU

Page 1: ...ply ON OFF remote control and DC OK The HE1U 5012 BC MU comes with a 3 year warranty The new internal Remote Monitoring and Control Unit RMCU provides the ability to remotely monitor the AC voltage po...

Page 2: ...19 W x 14 D Weight 9 1 lbs RMCU SPECIFICATIONS Hardware Revision 2 0 Firmware Revision 2 7 Network Connector RJ 45 10 100 Ethernet with activity LEDs Backup Battery CR2032 Memory Card 4GB Micro SD Vol...

Page 3: ...isconnect voltage INSTALLER NOTES NOTE DO NOT block any of the cooling vents on the sides and top and always allow adequate ventilation by not installing the unit inside tightly closed spaces Physical...

Page 4: ...arm ON LOW Shorted Alarm OFF HIGH Open HE1U 5012 BC MU Wiring Layout This system setup will provide continuous power to the load and maintain the battery bank with a float charge circuit while AC powe...

Page 5: ...5 of 23 August 3 2016...

Page 6: ...ress of 70 B3 D5 6B 3 Write down the IP address of the HE1U 5012 BC MU then proceed to the section in this manual named Open a Web Connection to the HE1U 5012 BC MU Using Static HE1U 5012 BC MU IP and...

Page 7: ...fox internet Explorer etc and enter the IP address of the power supply on your network into the URL box on the browser see the screenshot below If you are unable to connect to the device with the brow...

Page 8: ...Login Enter the user name and password Factory default username and password are as follows Admin Users have full control of the device Username admin cannot be changed Password admin Control users ha...

Page 9: ...9 of 23 August 3 2016 NETWORK SETUP...

Page 10: ...SNMP traps you can search for training material online under SNMP Traps MIB Browsers and SNMP Monitoring The MIB file for the HE1U 5012 BC MU can be downloaded from the HE1U 5012 BC MU after you conn...

Page 11: ...ail Setup Enter the required email setup parameters given to you by your System Administrator You can also send a test email from this screen Firmware 2 7 adds the ability to configure a periodic stat...

Page 12: ...12 of 23 August 3 2016 DEVICE SETUP...

Page 13: ...e file size reaches 5MB Download all log files before deleting them With REV 2 3 Firmware the ability to log readings when an alarm occurs has been added To turn off periodic logging just enter 0 as t...

Page 14: ...14 of 23 August 3 2016 SENSOR SETUP...

Page 15: ...ee the Alarm Setup section for more information In the HE1U 5012 BC MU the Digital Output 1 is an alarm output and Digital Output 2 controls the ON OFF state of the power supply The user must be logge...

Page 16: ...16 of 23 August 3 2016 ALARM SETUP...

Page 17: ...17 of 23 August 3 2016...

Page 18: ...added the ability to log alarms The Log Alarms setting on the Device Setup Page is the same as the Global Settings Log All Alarms setting on this page Digital output alarm conditions can be set to Nev...

Page 19: ...be taken when changing any of these settings NOTE To hard reset your device back to factory settings press the red button on the HE1U 5012 BC MU PCB and hold it for more than 30 seconds You will need...

Page 20: ...August 3 2016 REMOTE MONITORING AND CONTROL STATUS PAGE Status screen This screen shows the status of all analog and digital inputs A user can also download the Log file from this page AC Voltage is a...

Page 21: ...devices Just use the same IP address and add m for example 192 168 100 220 m HE1U 5012 BC MU MAINTENANCE Battery The battery on the HE1U 5012 BC MU is used to back up the real time clock for logging p...

Page 22: ...Copper ferrules prevent the current transfer from being influenced by dissimilar metals and remove the risk of corrosion Always use the correct tool to crimp the ferrule RECOMMENDED COPPER WIRE SIZE F...

Page 23: ...prior to inclusion of such changes DuraComm requires any product needing in or out of warranty service to be returned to DuraComm All requests for warranty service must be accompanied by proof of pur...

Reviews: