5–4
975-0347-01-01
No output voltage. Fault
Light is on.
Low input voltage
High input voltage
Thermal shutdown
Unit overload
Output is short circuited.
Recharge the battery; check the
connections and cable.
Make sure the Duracell is connected to
a 12 V battery.
Check the voltage regulation of the
charging system.
Allow the unit to cool off. Reduce the
load if continuous operation is
required.
Improve ventilation. Make sure the
inverter’s ventilation openings are not
obstructed.
Reduce the ambient temperature.
Reduce the load. Make sure the load
does not exceed the Duracell’s output
rating.
Remove the short circuit.
Low battery alarm stays on.
Poor DC wiring; poor battery
condition
Use proper cable size and lengths and
make solid connections.
Charge the battery.
Install a new battery.
Unit does not restart after a
fault condition.
Unit is restarted too soon.
Turn off the unit then wait about 3 to 5
seconds before turning it on again.
Table 5-1
Troubleshooting Reference
Problem
Possible Cause
Solution
Duracell1000.book Page 4 Friday, September 7, 2007 1:47 PM