![Duracell inverter 1000 Owner'S Manual Download Page 27](http://html.mh-extra.com/html/duracell/inverter-1000/inverter-1000_owners-manual_2540874027.webp)
3–8
975-0347-01-01
Calculating Fuse/Circuit Breaker Size
Because your batteries can provide thousands of amps of short-circuit
current, you need fuses or circuit breakers that can safely withstand the
short-circuit current that the batteries can produce.
To select the correct fuse type and size:
1. Determine the total short-circuit current rating for your batteries. For
example:
•
If you are using one battery to power your inverter and its short-
circuit current rating is 500 A, the total short-circuit current rating
is 500 A.
•
If you are powering your inverter with two 12 V batteries
connected in parallel, and each battery has a short-circuit current
rating of 500 A, the total short-circuit current rating is 1000 A.
•
If you are powering your inverter with two 6 V batteries
connected in series, and each battery has a short-circuit current
rating of 500 A, the total short-circuit current rating is 500 A.
2. Once you have determined the total short-circuit current rating of
your batteries, pick the fuse/circuit breaker’s interrupt capacity based
on the short-circuit current calculated in step 1.
3. Pick the fuse/circuit breaker’s current rating based on the product
used: 150 Adc
Fuses can be bought at any marine supply store, RV supply store, or
electrical products store.
Important:
For batteries connected in parallel, the total short-circuit current
rating is the sum of the short-circuit current ratings of all of the batteries
connected in parallel. For batteries connected in series, the total short-circuit
current rating is equal to the short-circuit rating of a single battery.
Duracell1000.book Page 8 Friday, September 7, 2007 1:47 PM
Summary of Contents for inverter 1000
Page 1: ...Owner s Guide 975 0347 01 01 REV B Printed in China t 1 408 987 6359 www xantrex com support ...
Page 2: ...Owner s Guide ...
Page 13: ...xii ...
Page 19: ...2 4 ...
Page 35: ...3 16 ...
Page 47: ...A 2 975 0347 01 01 Mounting Templates ...
Page 59: ...C 4 ...