D.10 CONDENSER FAN (If fitted)
SYMPTOMS OF THE FAULT
The refrigerator is too warm and the compressor is a not run very frequently.
How to confirm this fault
When the compressor is running look to see if the condenser fan is rotating.
If it is rotating this is not the problem. Proceed to the next check in the faultfinding
chart.
If it is not rotating a fault if indicated, see below for the action you should take.
Repair action required
1. Switch off the regulator.
2. Disconnect the fan wires from the compressor controller. Check the continuity of
each wire. If a break in a wire is detected replace the wire.
3. Clean the connections and reconnect the fan wires to the compressor controller.
4.Check to see if the fan can freely rotate. If it is jammed remove the item that is
stopping it from rotating.
5.Switch ON the refrigerator.
6. If the fan now rotates when the compressor is running the fault has been repaired.
7.If the fan still does not rotate replace the fan as described on page 86.
Summary of Contents for VC150
Page 1: ......
Page 3: ...3 SECTION I ...
Page 4: ...4 ...
Page 24: ...24 MODULE AND BATTERY WIRING DIAGRAMS SYSTEM WIRING DIAGRAM ...
Page 25: ...25 SYSTEM WIRING DIAGRAM GENERAL LAYOUT DIAGRAM ...
Page 26: ...26 GENERAL LAYOUT DIAGRAM ELECTRICAL CIRCUIT DIAGRAM ...
Page 27: ...27 ELECTRICAL CIRCUIT DIAGRAM REFRIGERATION CIRCUIT DIAGRAM ...
Page 28: ...28 REFRIGERATION CIRCUIT DIAGRAM ...
Page 29: ...29 SECTION II ...
Page 38: ...38 ...
Page 39: ...39 ...
Page 42: ...42 ...
Page 44: ...44 ...
Page 50: ...50 ...
Page 124: ...124 ANNEX 1 COMPONENT LAYOUTS OF SOME COMMONLY USED SOLAR REFRIGERATOR ...
Page 125: ...125 ...
Page 126: ...126 ...
Page 127: ...127 ...
Page 128: ...128 ...
Page 129: ...129 ...
Page 130: ...130 ANNEX II ADDITIONAL EPI TOOL KIT NEEDED FOR PHOTOVOLTAIC REFRIGERATOR REPAIR ...
Page 136: ...136 ...
Page 137: ...137 ...