Installation
28
4.1.3 USB SLAVE (FIRMWARE UPDATE) CONNECTOR
CAUTION!: Care must be taken not to overload the PCs USB system by connecting more
than the recommended number of USB devices to the PC. For further information, consult the
PC supplier.
NOTE: For further details of module configuration, refer to DSE Publication: 057-128
DSE8005 SCADA Suite Software Manual.
NOTE: The USB connection cable between the PC and the module must not be extended
beyond 6 m (20 feet). For distances over 6 m, it is possible to use a third party USB extender.
Typically, they extend USB up to 50 m (55 yards). The supply and support of this type of
equipment is outside the scope of Deep Sea Electronics PLC.
Description
Cable
Size
Notes
Socket for connection to PC with DSE
Configuration Suite Software for firmware
upgrades.
0.5 mm²
AWG 20
This is a standard USB type A
to type B connector.
4.1.4 USB HOST (CONFIGURATION) CONNECTOR
NOTE: For further details of module configuration, refer to DSE Publication: 057-128
DSE8005 SCADA Suite Software Manual.
NOTE: For further details on how to utilise a USB storage device for module
configuration, refer to section entitled Configuration (Graphical Interface Setup) elsewhere in
this document.
Description
Storage
Size
Notes
Socket for connection to USB storage
device for configuration
Maximum
16 GB
USB storage device formatted as FAT, not FAT32.