DSC PowerSeries PC1404 V1.1 Installation Manual Download Page 6

v

PC1404 Wiring Diagram

200–350 mA

85

1404

-31X

2-WIRE SMOKE DETECTORS

For NA 

installations 

only

 4.0/7.0 Ah

LCD5511

LED5511

PC1555RKZ

PK5500/PK5501

PK5508/PK5516

PC1404RKZ

US: F53AL01BPC1404
IC:160A-PC1404

(NA)

(EU)

FUSE 315mA/250V

(within terminal block)

ZONE DOUBLING

1500

BROWN

GREEN

RED

GOLD

2400

RED

YELLOW

RED

GOLD

-

-

2200 Ohm

END-OF-LINE

 RESISTOR

EOLR-3

RM-1/RM-2 POWER LOOP

SUPERVISORY RELAY

EOLR-2

END-OF-LINE

 RESISTOR

5600 Ohm, 0.5W

ALARM
INITIATING
LOOP
RESISTANCE
100 Ohm

12V

DC

o

.

is UL listed 

-

WARNING: Incorrect connection of batteries may result in battery rupture or 

fire hazard. Do NOT allow metal objects to connect the positive and 

negative terminals. Ensure that batteries are connected with correct polarity 

[Red to (+), Black to (-)]. Failure to comply with this may result in battery 

rupture and/or fire hazard. 

30

CON1

BAT+BAT-

RED

BLK

 

so s

I

-49

(32 120 F)

Use a UL/CSA-listed Class 2 Transformer 
16.5V

AC

 40 VA DSC PTD 1640U (USA)/

PTD 1640 (CDN). 
D

O

 not connect transformer to 

receptacle controlled by a switch. 

T-1

R-1
TIP

RING

RJ-31X

RED

GRN

BRN

GRA

Telephone line wiring

UL

For EU 

installations 

only

REFER TO 
MANUAL FOR
LIST OF 
COMPATIBLE 
DEVICES

 4-WIRE SMOKE DETECTORS

0

-

(for UL/ULC applications)

Refer to the 

Installation Guide (29008503) 

and 

User Manual (29008622) 

for complete

operating instructions.  

In Canada, the PC1404 is listed for Residential Fire and Burglary installations. The product 
shall be installed as per UL-S540 and ULC-S310 Standards. 

26 AWG

AUX Wiring

Use No. 14-22 AWG conductor. 
Total current draw from keypads, 
PGM outputs and AUX circuits must 
not exceed 550mA.

SIA-FAR Minimum System 

Requirements:

 1  PC1404 Panel

 1 Local annunciation devices

Local annunciation devices may be

any combination of these keypads:

PK5500, PK5501, PK5508, PK5516, 

PC1404RKZ, LCD5511, LED5511Z, 

PC1555RKZ

 

 

Battery capacity for 4 h standby is 
at least 4 Ah. Battery capacity for 24 h 
standby is 7 Ah. (Max. Aux current shall
be in accordance with Section 2.2 battery
connection.) Recommended batteries:
 DSC BD4-12 or DSC BD7-12. 

PC14-1

24

13.7

FSA-210B Series

NOTE

:

 Refer to the FSA-210 Installation Manual for more details.

NAME

MODEL

MAX #

BASE

COMPATIBILITY ID

DSC

NONE

FS200

SEE NOTE

Applicable UL Standards

UL 985 Household Fire Warning System Units
UL1023 Household Burglar Alarm System Units
UL 1635 Digital Alarm Communicator System Units
ANSI/SIA CP-01-2010

(a) The delay (power-up) time marked on the installation wiring diagram of the smoke detector 
or on the installed smoke detector(s) is to be used. Control panel is suitable for the following
UL installations: 

Installation Type 

Signalling Means

Resi Fire Burg   

DACT

Note: It is the installer’s responsibility to 
ensure that the external PRIMARY wires 
are tied together using a cable tie or 
equivalent as close as possible 
to the terminal block. 

UL compatibility ID for FSA-210B
series is FS200; for ULC listed
installations, use FSA-210A and
FSA-410A series. 

Test the alarm system at least 
once per week. 

THIS UNIT INCLUDES AN ALARM VERIFICATION FEATURE THAT WILL RESULT IN A 
DELAY OF THE SYSTEM ALARM SIGNAL FROM THE INDICATED CIRCUITS. THE 
TOTAL DELAY (CONTROL UNIT PLUS SMOKE DETECTORS) SHALL NOT EXCEED 60 
SECONDS. NO OTHER SMOKE DETECTOR SHALL BE CONNECTED TO THESE 
CIRCUITS UNLESS APPROVED BY THE LOCAL AUTHORITY HAVING JURISDICTION.
Note: Alarm Verification is not supported for 2-wire interface, only 4-wire.

.

230/240 VAC
50/60Hz

Summary of Contents for PowerSeries PC1404 V1.1

Page 1: ...on Guide WARNING This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer The entire manual should be c...

Page 2: ...damage For direct plug in versions use the transformer supplied with the device WARNING THIS EQUIPMENT WHEN POWERED VIA DIRECT PLUG IN TRANSFORMER HAS NO MAINS ON OFF SWITCH THE PLUG OF THE DIRECT PL...

Page 3: ...Smoke detectors should always be installed in USA in accordance with Chapter 29 of NFPA 72 the National Fire Alarm Code 29 5 1 1 Where required by other governing laws codes or standards for a specifi...

Page 4: ...ructions They cannot discriminate between intruders and intended occupants Motion detectors do not provide volumetric area protection They have multiple beams of detection and motion can only be detec...

Page 5: ...Zones 7 3 Keypad Commands 10 3 1 Arming and Disarming 10 3 2 Auto Bypass Stay Arming 10 3 3 Automatic Arming 10 3 4 Night Arming 10 3 5 Commands 10 4 Programming 16 4 1 Installer Programming 16 4 2 Pr...

Page 6: ...R Minimum System Requirements 1 PC1404 Panel 1 Local annunciation devices Local annunciation devices may be any combination of these keypads PK5500 PK5501 PK5508 PK5516 PC1404RKZ LCD5511 LED5511Z PC15...

Page 7: ...ersons only service person is defined as a person having the appropriate technical training and experience necessary to be aware of hazards to which that person may be exposed in performing a task and...

Page 8: ...GS3060 GPRS Universal Cellular Alarm Communicator 120 3 1 3 2 3G3070 HSPA 3G Universal Cellular Alarm Communicator 120 3 5 GS3105 3125 K BA Wireless Alarm Communicator 250 excluding outputs 3 0 UL ULC...

Page 9: ...protection fixed at 9 6V Aux Voltage 11 1 12 5VDC Current 550mA Max Note Aux and PGM outputs share the 550mA load Keybus Terminals Clock yellow Data green Memory 32Kbit serial CMOS EEPROM with write...

Page 10: ...Please verify that all modules appear on the system according to the instructions in Section 2 6 Keypad Assignment Step 9 Programming the System Sections 4 5 Section 4 Programming explains how to pro...

Page 11: ...and metallic plating requirements of 47 C F R Part 68 SubPart F For proper operation no other telephone equipment should be connected between the control panel and the tele phone company facilities D...

Page 12: ...key twice to exit programming d After assigning all keypads perform a supervisory reset by entering 8 Installer Code 902 The panel will reset supervision and re enroll modules on the system How to Pro...

Page 13: ...To enable zone doubling Section 13 Option 7 must be ON All zones must be wired according to the following diagram Only Normally Closed devices can be used with zone doubling Note All resistors are 5 t...

Page 14: ...d of line supervision connect the zone according to one of the configurations outlined in Section 2 9 Zone Wiring End of line resistors must be placed on the device end of the loop not at the keypad N...

Page 15: ...RED positive terminal and the black wire to the BLK negative terminal When using end of line supervision connect the zone according to one of the configurations outlined in your system s Installation...

Page 16: ...off press 5 5 To control whether the LED indicates AC present or absent press 6 6 When complete press to exit Backlighting Intensity Adjustment The keypad has 5 backlighting intensity settings To adj...

Page 17: ...ad Function Programming in PC1404 Pro gramming Descriptions 3 3 Automatic Arming The system can be programmed to arm at the same time each day Upon entry of this section enter 4 digits for the 24 Hour...

Page 18: ...stem is armed in the Stay mode by a arming and not exiting through a delay zone during the exit delay or b pressing a function key programmed for Stay Arm or Arming Without Entry Delay 9 the zones pro...

Page 19: ...fter the AC fail transmission delay if Trouble 2 is NOT present 2 AC Failure There is no audible annunciation on AC power failure unless trouble beeps on AC failure are enabled in Section 018 Option 8...

Page 20: ...still squawk 8 One Time Use Code When the one time use code is entered on the system the user of the code will be able to arm the panel with the code as many times as they want They will also be able...

Page 21: ...te using the following format HH MM MM DD YY Program the time using military standard e g 8 00 pm 20 00 hours Valid entries for the Hour are 00 23 Valid entries for the Minute are 00 59 2 Auto Arm Con...

Page 22: ...n Stay Mode or Armed in Away Mode for this closing type 0 Quick Exit When armed press 0 to activate Quick Exit Quick Exit allows the user 2 minutes to exit the premises through any delay zone with out...

Page 23: ...one digit in each box in the programming section in order for the change to be valid 4 2 Programming Decimal Data A set number of programming boxes are allotted for each section requiring decimal dat...

Page 24: ...ED and Fixed Message LCD Keypads Any programming section can be viewed from an LED keypad When a programming section is entered the keypad will immediately display the first digit of information progr...

Page 25: ...330 Tamper Rep Codes 26 334 Tamper Restore Rep Codes 26 338 Misc Tamper Rep Codes 26 339 340 Closing Arming Rep Codes 26 341 Misc Closing Arming Rep Codes 26 342 343 Opening Disarming Rep Codes 26 344...

Page 26: ...7 1 Reactivate Stay Away Zones 26 33 Future Use This function key must not be used in CP 01 listed systems Key 1 Key 2 Key 3 Key 4 Key 5 Keypad Defaults BBB BBB BBB BBB BBB 00 Null Zone Not Used 14 24...

Page 27: ...____I 123456 I_______I_______I_______I_______I_______I_______I AAAA00 I_______I_______I_______I_______I_______I_______ Programmable Output Options 00 Null PGM Not Used 01 Burglary and Fire Output 02 N...

Page 28: ...e Doubling Enabled Zone Doubling Disabled 8 Temporal Three Fire Signal Enabled Standard Pulsed Fire Signal Note When Option 7 is ON the configuration of Options 1 and 2 should be ignored Opt Def ON OF...

Page 29: ...Enabled ON for SIA CP 01 Exit Delay Restart Disabled 8 System AC Failure Trouble Beeps Enabled System AC Failure Trouble Beeps Disabled Default 00 I_______I_______I Keypad Address 1 Zone Valid entries...

Page 30: ...lsed No No No No No 00 Null Zone 01 Delay 1 02 Delay 2 03 Instant 04 Interior 05 Interior Stay Away 06 Delay Stay Away 07 Delay 24 hr Fire Hardwired 08 Stand 24 hr Fire Hardwired 09 24 hr Supervisory...

Page 31: ...20 24 hr Freeze 21 24 hr Latching Tamper 22 Momentary Keyswitch Arm 23 Maintained Keyswitch Hardwired 24 Not Used 25 Interior Delay 26 24 hr Non Alarm 27 30 Not Used 31 Day Zone 32 Instant Stay Away 3...

Page 32: ...__I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I____I 302 Second Telephone Number 32 Digits I__D___I_____I_____I_...

Page 33: ...__ ___ ___ ___ ___ ___ ___ General System Tamper ___ ___ General System Tamper Restore ___ ___ Keypad Lockout Section 339 Code 1 Code 2 Code 3 Code 4 Code 5 Code 6 Code 7 Code 8 ___ ___ ___ ___ ___ __...

Page 34: ...___ AC Failure Trouble Restore ___ ___ General System Trouble Restore ___ ___ Bell Circuit Trouble Restore ___ ___ General System Supervisory Restore ___ ___ Fire Trouble Restore ___ ___ System Reset...

Page 35: ...I_______I______I_______I Swinger Shutdown Tampers and Rest 001 014 Transmissions 001 006 for CP 01 000 disabled 003 I_______I______I_______I Swinger Shutdown Maint and Rest 001 014 Transmissions 001...

Page 36: ...ting Cancel Disabled 5 For Future Use For Future Use 6 AC Failure Communications Delay is in Hours AC Failure Communications Delay is in Minutes 7 Number of Dialing Attempts for Residential Dial is 1...

Page 37: ...__ ___ ___ ___ ___ ___ ___ ___ PC5208 503 PGM 3 ___ ___ ___ ___ ___ ___ ___ ___ 504 PGM 4 ___ ___ ___ ___ ___ ___ ___ ___ 505 PGM 5 ___ ___ ___ ___ ___ ___ ___ ___ 506 PGM 6 ___ ___ ___ ___ ___ ___ __...

Page 38: ...bled Disabled Disabled 09 System Trouble Attribute 1 2 3 4 5 6 7 8 ON OFF Burglary Event Fire Event Panic Event Medical Event Supervisory Event Priority Event Duress Event Output Follows Timer Disable...

Page 39: ...ode 35 Code 36 Code 37 Code 38 Code 39 Code 40 ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ Code 33 Code 34 Code 35 Code 36 Code 37 Code 38 Code 39 Code 40 ___ ___ ___ ___ ___ ___ _...

Page 40: ...5 Programming Worksheets 33 991 Installer Lockout Disable 999 Restore Panel Factory Defaults Enter 991 Installer s Code 991 Enter 999 Installer s Code 999...

Page 41: ...red Press 1 to determine specific trouble 1 Low Battery Main panel battery less than 11 1 VDC Note This trouble condition will not clear until the battery voltage is 12 5 VDC min under load Note If ba...

Page 42: ...across AC terminals is 16 18VAC Replace transformer if required Trouble 2 AC Failure AC Failure No AC at panel AC input terminals Verify voltage measured across AC terminals is 16 18VAC Replace transf...

Page 43: ...e trouble condi tion clears A short circuit is present on one or more zones with double end of line resistors enabled Remove the wire leads from Z and COM terminals and measure the resistance of the w...

Page 44: ...nt when the system is disarmed after an alarm but before the expiry of the alarm cancellation timer A R E 4 A6 UUU OC UU 329 F Key Alarm Rest Keypad fire alarm alarm and restore rep codes sent togethe...

Page 45: ...delinquency has expired without zone activity or without system being armed MA R E 6 54 000 CD 00 347 Installer Lead In Installer s mode has been entered MA R E 6 27 000 LB 00 347 Installer Lead Out...

Page 46: ...upervisory Buzzer UA ZZ UH ZZ E 1 4A ZZZ E 1 4A ZZZ 24 Hr Burg BA ZZ BH ZZ E 1 3A ZZZ E 1 3A ZZZ 24 Hr Gas GA ZZ GH ZZ E 1 51 ZZZ E 1 51 ZZZ 24 Hr Heat KA ZZ KH ZZ E 1 58 ZZZ E 1 58 ZZZ 24 Hr Medical...

Page 47: ...the account number substitute the HEX digit A for the 0 All reporting codes must be two digits If the digit 0 is in the reporting code substitute the HEX digit A for the 0 To prevent the panel from re...

Page 48: ...vate line format allows the communication of zone alarms directly to a user over a telephone line When an event occurs that the panel is programmed to commu nicate the panel seizes the line and dials...

Page 49: ...ements adopted by the ACTA On the side of this equipment is a label that contains among other information a product identifier If requested this number must be provided to the Telephone Company Produc...

Page 50: ...tions Delay Abort Window shall not exceed 60s Range 20 45 sec Default 30 sees Required programmable Abort Annunciation 382 Option 3 ON Enables the Communication Cancelled message display on keypad Ann...

Page 51: ...e minimum Bell Time out is 4 minutes Refer to section 005 Note For ULC Residential Fire Installations the minimum Bell Time out is 5 minutes Temporal Three Fire Signal shall be enabled Refer to sectio...

Page 52: ...ption 6 Audible Exit Fault Enable OFF 168 21 SetClockForward DaylightSaving Month 009 Week 005 169 21 SetClockBack StandardTime Month 004 Hour 003 320 22 Alarm Reporting Codes Zones 01 08 11 329 23 Pr...

Page 53: ...estart Enabled Exit Delay Restart Disabled ON 023 19 Tenth System Options Option 5 Switching from Away to Stay Disabled Away to Stay Toggle Option Permitted ON 101 108 20 Zone Attributes Defaults 01 0...

Page 54: ...Supervisory Restore 33 347 24 Misc Maintenance Reporting Codes Telephone 1 2 FTC Restore 54 DLS Lead in and Lead out FF General Zone Fault Alarm 80 General Zone Fault Restore 80 Delinquency Reporting...

Page 55: ...Buzzer Follows Bell Disabled ON 168 21 Daylight Savings Time Begins Month 004 Week 001 169 21 Daylight Savings Time Ends Month 010 Week 005 328 22 Miscellaneous Alarm Reporting Codes Recent Closing 00...

Page 56: ...WV DQG RWKHU UHOHYDQW SURYLVLRQV RI LUHFWLYH 7KH FRPSOHWH 5 77 HFODUDWLRQ RI RQIRUPLW FDQ EH IRXQG DW KWWS ZZZ GVF FRP OLVWLQJVBLQGH DVS 6 MDNR Y UREFH SURKOD XMH H WHQWR Y UREHN MH Y VRXODGX VH Y HPL...

Reviews: