
2 Installation
2.11 Fire Zone Wiring
All 4-wire smoke detectors must be wired according to the fol-
lowing diagram:
All 2-wire smoke detectors must be wired according to the fol-
lowing diagram:
2-wire smoke detector initiating circuit:
•
Style B (Class B), Supervised, Power Limited
•
UL Compatibility Identifier . . . . . . . . . . . . . . . . PC14-1
•
DC Output Voltage . . . . . . . . . . . . . . . . . . 9.3-13.7 VDC
•
Detector Load . . . . . . . . . . . . . . . . . . . . . . . .2mA (Max.)
•
Single-end-of-line (SEOL) resistor. . . . . . . . . . . . 2200
•
Loop resistance . . . . . . . . . . . . . . . . . . . . . . .24
(Max.)
•
Standby impedance . . . . . . . . . . . . . . . . . 1250
(Nom.)
•
Alarm impedance . . . . . . . . . . . . . . . . . . . .650
(Max.)
•
Alarm current . . . . . . . . . . . . . . . . . . . . . . .94mA (Max.)
2.12 CO Detector Wiring
The following CO detector models can be used with PC1404
v1.0 and higher control panels:
•
Potter Model CO-12/24, UL File E321434
•
Quantum Model 12-24SIR, UL File E186246
•
NAPCO Model FW-CO12 or FW-CO1224, UL File
E306780
•
System Sensor Model CO1224, UL File E307195
2.13 Keypad Zones
Each “z” keypad on the system has a zone input to which a
device - such as a door contact - can be connected. This elimi-
nates the need to run wires back to the control panel for every
device.
To install the keypad, open the keypad plastic at the bottom of
the unit. Locate the five terminals on the keypad circuit board.
Connect the four Keybus wires from the control panel: the red
wire to R, the black to B, the yellow to Y and the green to G.
To connect the zone, run one wire to the Z terminal and the other
to B. For powered devices, use red and black to supply power to
the device. Run the red wire to the R (positive) terminal and the
black wire to the B (negative) terminal.
When using end of line supervision, connect the zone according
to one of the configurations outlined in Section 2.9 Zone Wiring.
End of line resistors must be placed on the device end of the
loop, not at the keypad.
Note:
Only non 24-hr burglary zones can be configured as key-
pad zones for UL Listed products.
Assigning Keypad Zones
When using keypad zone inputs, each input used must be
assigned a zone number in Installer Programming.
1.
Ensure that you have enrolled all installed keypads into the
desired slots. (See Section 2.6 Keypad Assignment.)
2.
Enter [*][8] [Installer Code] to go to Installer Program-
ming.
3.
Enter Section [20] for Keypad Programming. There are
eight programming locations in this section, one for each
keypad slot.
4.
Enter a 2-digit number (01-08) to specify which zone num-
ber should be assigned to the keypad slot. This number
must be entered in the location corresponding to the keypad
to which each zone is connected.
5.
Press [#] twice to exit Installer Programming.
Example
: The zone on an PK5500 keypad in Slot 8 is to be
assigned Zone 3. In Section [020], scroll to Option [8] and enter
(03).
Note:
Keypad Zones 1-4 will replace Zone terminals Z1-Z4 on
the control panel.
Note:
Once the keypad zones are assigned, you must also pro-
gram zone definitions and zone attributes. (See also 5.2 Pro-
Note:
Keypad zones can only be used for household burglary-
initiated devices. Do not place the device more than 3 feet from
the keypad. The keypad zone must be tested weekly.
CO DETECTOR
RM-1/RM-2
POWER LOOP
SUPERVISORY
RELAY
(12V
DC
, 35mA)
ALARM
INITIATING
LOOP
RESISTANCE
100 ohm
SEOL
RESISTOR
(5600 ohm)
PC1404
ANY
COM
ZONE
INPUT
POWER
ALARM
TROUBLE
NC
C
NO NC
C
NO
ANY
Z
(SEOL TYPE 41)
AUX
+
+
-
-
+
-