DSC PowerSeries PC1404 V1.1 Installation Manual Download Page 19

PC1404

12

Viewing of troubles is now permitted while armed. The various troubles are described below: 

[

*

][3] Alarm Memory

When Disarmed, press [*] then [3] to enter the alarm memory mode. The “Memory” light will flash and any alarm caused during the

last armed period will be displayed on the zone lights. 
Press [#] to return to the “Ready” mode. If [#] is not pressed, the keypad will time out in 30 seconds.
There is no memory of previous armed states. The Event Buffer can be used to achieve this function.

[

*

][4] Door Chime On/Off Command

When Armed/Disarmed, to turn the feature on or off, enter [*][4].The Door Chime feature is used to sound a tone from the keypad

whenever a zone programmed as a Chime type is activated. When the Door Chime feature is turned ON, the keypad will beep several

times whenever a Chime zone is activated. When the feature is being turned ON, the keypad will beep 3 times and the LCD will display

“Door Chime Feature ON”. When the feature is being turned OFF, the keypad will sound a single long tone and the LCD keypad will

display “Door Chime Feature OFF”.

[*][5] Program User Codes

The following table identifies available user codes:

When Disarmed, enter [*][5] to access the attribute programming mode. 
1) The default attributes of a new code will be the attributes of the code used to enter [*][5] whether it is a new code or an existing code

being programmed.
2) All user codes will now have a check so that they cannot be + or -1 of any other code.

Light

Trouble

1

Service Required:

 

Press [1] to determine the specific trouble. Lights 1–8 will light up to indicate the trouble.

Light [1] Low Battery: The standby battery's voltage is measured under load every 3 minutes and during a System Test.

The limits of alarms and restores are determined by the Swinger Shutdown (Maintenance Troubles & Restores) counter.

Set at 3 by default, there will be 3 Low Battery Troubles and 3 Low Battery Restores before latching. The latching is reset

at midnight or upon arming.

Light [2] Bell Circuit Trouble: If the bell circuit is overdrawn or the bell circuit is open, a keypad trouble is generated and a

Bell Circuit Trouble can be reported. 

Light [3] General System Trouble: Any peripheral module trouble will be indicated and communicated with a General

Trouble, but logged to the event buffer with a detailed description.

Light [4] General System Tamper: Any peripheral module tamper will be indicated and communicated with a General

Tamper but logged to the event buffer with a detailed description.

Light [5] General System Supervisory: If the system loses Supervisory signals from a peripheral module, this will be indi-

cated and communicated with a General Supervisory but logged to the event buffer with a detailed description.

Light [6] Not used. 

Light [7] PC5204 Low Battery: The PC5204 Module has detected a Low Battery Condition. 

Light [8] PC5204 AC Fail: The PC5204 Module has detected an AC Power Failure. This Trouble will initiate the keypad

trouble beeps after the AC fail transmission delay if Trouble #2 is NOT present.

2

AC Failure:

 

There is no audible annunciation on AC power failure unless trouble beeps on AC failure are enabled in

Section [018] Option [8]. The system “Trouble” light will come ON but the audible indication will not sound until there is a

low battery condition. Transmission delay can be programmed for 000 to 255 minutes/hours. If the AC Fails, the battery

will be continuously checked until the panel shuts down.

3

Telephone Line Monitoring Trouble (TLM):

The telephone line voltage is measured every 3 seconds. If the volt-

age drops below 1 to 3 volts for the number of consecutive checks programmed in Section [377], a Telephone Line Trou-

ble is generated. This additional check denomination may fluctuate from board to board, as it is dependant on hardware

component tolerances. The TLM Restore shall occur when the value in Section [377] is reached.

4

Failure to Communicate (FTC):

 

If the digital communicator is unsuccessful in communicating with any of the pro-

grammed telephone numbers, a failure to communicate trouble will be generated. If a later attempt to communicate is

successful, the panel can also transmit the FTC restore reporting code and all previous unsuccessful events. If the digital

communicator is unsuccessful in communicating with any of the programmed telephone numbers, a failure to communi-

cate trouble will be generated. If a later attempt to communicate is successful, the panel can also transmit the FTC

restore reporting code and all previous unsuccessful events. 

5

Zone Fault (including Fire Zone):

 

If any zone on the system is in the Trouble state, this trouble will be generated.

For hardwired zones (excluding Fire) using double end of line supervision, this is the shorted state. If DEOL is not used,

Zone Troubles can still be generated on Fire Zones (open state). If [5] is pressed in the Trouble mode, the keypad will

now display all of the zones in trouble. Fire Zone Faults are identified in the Event Buffer. They log a “Fault Zone X” fol-

lowed by a generic “Fire Trouble”. This has been done so that intermittent wiring problems may be tracked down via the

Event Buffer. 

This trouble will be generated and displayed in the armed state if a Fire trouble is present. It will also  restart  the  Trouble

beeps. If any zone enters this Trouble state (short), the keypad buzzers will sound trouble beeps to annunciate the condi-

tion. 

6

Zone Tamper:

 

This trouble is used with DEOL Zone Supervision only. If any zone is in the Tamper state, this trouble will

be generated. Zones excluded from this are Fire and zones not supporting the DEOL configuration (LINKS answer, Key-

switch). Press [6] in the Trouble mode to display all of the tampered zones. If any zone enters this Tamper state (open), the

keypad buzzers will sound trouble beeps to annunciate the condition.

 

7

Not Used

8

Loss of System Time:

 

When the panel is powered up, the internal clock needs to be set to the correct time. This trou-

ble is cleared when an attempt is made to reset the clock.

Code

Type

Function

[01] – [39]

[40]

General User Codes

Master Code

Determined by attributes programmed below

Summary of Contents for PowerSeries PC1404 V1.1

Page 1: ...on Guide WARNING This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer The entire manual should be c...

Page 2: ...damage For direct plug in versions use the transformer supplied with the device WARNING THIS EQUIPMENT WHEN POWERED VIA DIRECT PLUG IN TRANSFORMER HAS NO MAINS ON OFF SWITCH THE PLUG OF THE DIRECT PL...

Page 3: ...Smoke detectors should always be installed in USA in accordance with Chapter 29 of NFPA 72 the National Fire Alarm Code 29 5 1 1 Where required by other governing laws codes or standards for a specifi...

Page 4: ...ructions They cannot discriminate between intruders and intended occupants Motion detectors do not provide volumetric area protection They have multiple beams of detection and motion can only be detec...

Page 5: ...Zones 7 3 Keypad Commands 10 3 1 Arming and Disarming 10 3 2 Auto Bypass Stay Arming 10 3 3 Automatic Arming 10 3 4 Night Arming 10 3 5 Commands 10 4 Programming 16 4 1 Installer Programming 16 4 2 Pr...

Page 6: ...R Minimum System Requirements 1 PC1404 Panel 1 Local annunciation devices Local annunciation devices may be any combination of these keypads PK5500 PK5501 PK5508 PK5516 PC1404RKZ LCD5511 LED5511Z PC15...

Page 7: ...ersons only service person is defined as a person having the appropriate technical training and experience necessary to be aware of hazards to which that person may be exposed in performing a task and...

Page 8: ...GS3060 GPRS Universal Cellular Alarm Communicator 120 3 1 3 2 3G3070 HSPA 3G Universal Cellular Alarm Communicator 120 3 5 GS3105 3125 K BA Wireless Alarm Communicator 250 excluding outputs 3 0 UL ULC...

Page 9: ...protection fixed at 9 6V Aux Voltage 11 1 12 5VDC Current 550mA Max Note Aux and PGM outputs share the 550mA load Keybus Terminals Clock yellow Data green Memory 32Kbit serial CMOS EEPROM with write...

Page 10: ...Please verify that all modules appear on the system according to the instructions in Section 2 6 Keypad Assignment Step 9 Programming the System Sections 4 5 Section 4 Programming explains how to pro...

Page 11: ...and metallic plating requirements of 47 C F R Part 68 SubPart F For proper operation no other telephone equipment should be connected between the control panel and the tele phone company facilities D...

Page 12: ...key twice to exit programming d After assigning all keypads perform a supervisory reset by entering 8 Installer Code 902 The panel will reset supervision and re enroll modules on the system How to Pro...

Page 13: ...To enable zone doubling Section 13 Option 7 must be ON All zones must be wired according to the following diagram Only Normally Closed devices can be used with zone doubling Note All resistors are 5 t...

Page 14: ...d of line supervision connect the zone according to one of the configurations outlined in Section 2 9 Zone Wiring End of line resistors must be placed on the device end of the loop not at the keypad N...

Page 15: ...RED positive terminal and the black wire to the BLK negative terminal When using end of line supervision connect the zone according to one of the configurations outlined in your system s Installation...

Page 16: ...off press 5 5 To control whether the LED indicates AC present or absent press 6 6 When complete press to exit Backlighting Intensity Adjustment The keypad has 5 backlighting intensity settings To adj...

Page 17: ...ad Function Programming in PC1404 Pro gramming Descriptions 3 3 Automatic Arming The system can be programmed to arm at the same time each day Upon entry of this section enter 4 digits for the 24 Hour...

Page 18: ...stem is armed in the Stay mode by a arming and not exiting through a delay zone during the exit delay or b pressing a function key programmed for Stay Arm or Arming Without Entry Delay 9 the zones pro...

Page 19: ...fter the AC fail transmission delay if Trouble 2 is NOT present 2 AC Failure There is no audible annunciation on AC power failure unless trouble beeps on AC failure are enabled in Section 018 Option 8...

Page 20: ...still squawk 8 One Time Use Code When the one time use code is entered on the system the user of the code will be able to arm the panel with the code as many times as they want They will also be able...

Page 21: ...te using the following format HH MM MM DD YY Program the time using military standard e g 8 00 pm 20 00 hours Valid entries for the Hour are 00 23 Valid entries for the Minute are 00 59 2 Auto Arm Con...

Page 22: ...n Stay Mode or Armed in Away Mode for this closing type 0 Quick Exit When armed press 0 to activate Quick Exit Quick Exit allows the user 2 minutes to exit the premises through any delay zone with out...

Page 23: ...one digit in each box in the programming section in order for the change to be valid 4 2 Programming Decimal Data A set number of programming boxes are allotted for each section requiring decimal dat...

Page 24: ...ED and Fixed Message LCD Keypads Any programming section can be viewed from an LED keypad When a programming section is entered the keypad will immediately display the first digit of information progr...

Page 25: ...330 Tamper Rep Codes 26 334 Tamper Restore Rep Codes 26 338 Misc Tamper Rep Codes 26 339 340 Closing Arming Rep Codes 26 341 Misc Closing Arming Rep Codes 26 342 343 Opening Disarming Rep Codes 26 344...

Page 26: ...7 1 Reactivate Stay Away Zones 26 33 Future Use This function key must not be used in CP 01 listed systems Key 1 Key 2 Key 3 Key 4 Key 5 Keypad Defaults BBB BBB BBB BBB BBB 00 Null Zone Not Used 14 24...

Page 27: ...____I 123456 I_______I_______I_______I_______I_______I_______I AAAA00 I_______I_______I_______I_______I_______I_______ Programmable Output Options 00 Null PGM Not Used 01 Burglary and Fire Output 02 N...

Page 28: ...e Doubling Enabled Zone Doubling Disabled 8 Temporal Three Fire Signal Enabled Standard Pulsed Fire Signal Note When Option 7 is ON the configuration of Options 1 and 2 should be ignored Opt Def ON OF...

Page 29: ...Enabled ON for SIA CP 01 Exit Delay Restart Disabled 8 System AC Failure Trouble Beeps Enabled System AC Failure Trouble Beeps Disabled Default 00 I_______I_______I Keypad Address 1 Zone Valid entries...

Page 30: ...lsed No No No No No 00 Null Zone 01 Delay 1 02 Delay 2 03 Instant 04 Interior 05 Interior Stay Away 06 Delay Stay Away 07 Delay 24 hr Fire Hardwired 08 Stand 24 hr Fire Hardwired 09 24 hr Supervisory...

Page 31: ...20 24 hr Freeze 21 24 hr Latching Tamper 22 Momentary Keyswitch Arm 23 Maintained Keyswitch Hardwired 24 Not Used 25 Interior Delay 26 24 hr Non Alarm 27 30 Not Used 31 Day Zone 32 Instant Stay Away 3...

Page 32: ...__I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I____I 302 Second Telephone Number 32 Digits I__D___I_____I_____I_...

Page 33: ...__ ___ ___ ___ ___ ___ ___ General System Tamper ___ ___ General System Tamper Restore ___ ___ Keypad Lockout Section 339 Code 1 Code 2 Code 3 Code 4 Code 5 Code 6 Code 7 Code 8 ___ ___ ___ ___ ___ __...

Page 34: ...___ AC Failure Trouble Restore ___ ___ General System Trouble Restore ___ ___ Bell Circuit Trouble Restore ___ ___ General System Supervisory Restore ___ ___ Fire Trouble Restore ___ ___ System Reset...

Page 35: ...I_______I______I_______I Swinger Shutdown Tampers and Rest 001 014 Transmissions 001 006 for CP 01 000 disabled 003 I_______I______I_______I Swinger Shutdown Maint and Rest 001 014 Transmissions 001...

Page 36: ...ting Cancel Disabled 5 For Future Use For Future Use 6 AC Failure Communications Delay is in Hours AC Failure Communications Delay is in Minutes 7 Number of Dialing Attempts for Residential Dial is 1...

Page 37: ...__ ___ ___ ___ ___ ___ ___ ___ PC5208 503 PGM 3 ___ ___ ___ ___ ___ ___ ___ ___ 504 PGM 4 ___ ___ ___ ___ ___ ___ ___ ___ 505 PGM 5 ___ ___ ___ ___ ___ ___ ___ ___ 506 PGM 6 ___ ___ ___ ___ ___ ___ __...

Page 38: ...bled Disabled Disabled 09 System Trouble Attribute 1 2 3 4 5 6 7 8 ON OFF Burglary Event Fire Event Panic Event Medical Event Supervisory Event Priority Event Duress Event Output Follows Timer Disable...

Page 39: ...ode 35 Code 36 Code 37 Code 38 Code 39 Code 40 ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ ___ Code 33 Code 34 Code 35 Code 36 Code 37 Code 38 Code 39 Code 40 ___ ___ ___ ___ ___ ___ _...

Page 40: ...5 Programming Worksheets 33 991 Installer Lockout Disable 999 Restore Panel Factory Defaults Enter 991 Installer s Code 991 Enter 999 Installer s Code 999...

Page 41: ...red Press 1 to determine specific trouble 1 Low Battery Main panel battery less than 11 1 VDC Note This trouble condition will not clear until the battery voltage is 12 5 VDC min under load Note If ba...

Page 42: ...across AC terminals is 16 18VAC Replace transformer if required Trouble 2 AC Failure AC Failure No AC at panel AC input terminals Verify voltage measured across AC terminals is 16 18VAC Replace transf...

Page 43: ...e trouble condi tion clears A short circuit is present on one or more zones with double end of line resistors enabled Remove the wire leads from Z and COM terminals and measure the resistance of the w...

Page 44: ...nt when the system is disarmed after an alarm but before the expiry of the alarm cancellation timer A R E 4 A6 UUU OC UU 329 F Key Alarm Rest Keypad fire alarm alarm and restore rep codes sent togethe...

Page 45: ...delinquency has expired without zone activity or without system being armed MA R E 6 54 000 CD 00 347 Installer Lead In Installer s mode has been entered MA R E 6 27 000 LB 00 347 Installer Lead Out...

Page 46: ...upervisory Buzzer UA ZZ UH ZZ E 1 4A ZZZ E 1 4A ZZZ 24 Hr Burg BA ZZ BH ZZ E 1 3A ZZZ E 1 3A ZZZ 24 Hr Gas GA ZZ GH ZZ E 1 51 ZZZ E 1 51 ZZZ 24 Hr Heat KA ZZ KH ZZ E 1 58 ZZZ E 1 58 ZZZ 24 Hr Medical...

Page 47: ...the account number substitute the HEX digit A for the 0 All reporting codes must be two digits If the digit 0 is in the reporting code substitute the HEX digit A for the 0 To prevent the panel from re...

Page 48: ...vate line format allows the communication of zone alarms directly to a user over a telephone line When an event occurs that the panel is programmed to commu nicate the panel seizes the line and dials...

Page 49: ...ements adopted by the ACTA On the side of this equipment is a label that contains among other information a product identifier If requested this number must be provided to the Telephone Company Produc...

Page 50: ...tions Delay Abort Window shall not exceed 60s Range 20 45 sec Default 30 sees Required programmable Abort Annunciation 382 Option 3 ON Enables the Communication Cancelled message display on keypad Ann...

Page 51: ...e minimum Bell Time out is 4 minutes Refer to section 005 Note For ULC Residential Fire Installations the minimum Bell Time out is 5 minutes Temporal Three Fire Signal shall be enabled Refer to sectio...

Page 52: ...ption 6 Audible Exit Fault Enable OFF 168 21 SetClockForward DaylightSaving Month 009 Week 005 169 21 SetClockBack StandardTime Month 004 Hour 003 320 22 Alarm Reporting Codes Zones 01 08 11 329 23 Pr...

Page 53: ...estart Enabled Exit Delay Restart Disabled ON 023 19 Tenth System Options Option 5 Switching from Away to Stay Disabled Away to Stay Toggle Option Permitted ON 101 108 20 Zone Attributes Defaults 01 0...

Page 54: ...Supervisory Restore 33 347 24 Misc Maintenance Reporting Codes Telephone 1 2 FTC Restore 54 DLS Lead in and Lead out FF General Zone Fault Alarm 80 General Zone Fault Restore 80 Delinquency Reporting...

Page 55: ...Buzzer Follows Bell Disabled ON 168 21 Daylight Savings Time Begins Month 004 Week 001 169 21 Daylight Savings Time Ends Month 010 Week 005 328 22 Miscellaneous Alarm Reporting Codes Recent Closing 00...

Page 56: ...WV DQG RWKHU UHOHYDQW SURYLVLRQV RI LUHFWLYH 7KH FRPSOHWH 5 77 HFODUDWLRQ RI RQIRUPLW FDQ EH IRXQG DW KWWS ZZZ GVF FRP OLVWLQJVBLQGH DVS 6 MDNR Y UREFH SURKOD XMH H WHQWR Y UREHN MH Y VRXODGX VH Y HPL...

Reviews: