16

● 

For a maximum performance, we recommend using supply

 

1. If the high supply temperature is not needed, supply 2

 

can be used so that all pipes are at the bottom of the fire.

● 

place the overpressure relief valve (figure 4) in the CH

 

discharge pipe of the fire and connect it to the water

 

discharge or sewer (also see chapter 3.5.2).

Between the overpressure relief valve and the fire, no valves 
or other resistors may be placed!

5.6.   Return temperature monitoring

In order to prevent the heat exchanger from becoming too 
contaminated, it is important to bring the fire as quickly as 
possible above the condensation temperature of the flue gases 
and to keep it at that temperature.  This should be done by 
means of return temperature monitoring, which will make sure 
that the return temperature to the fire does not get below 60˚C. 
Such a unit can be ordered at Dik Geurts under order no. 
45256. Application of such a system is necessary in order to 
guarantee a proper operation of this product. In appendix 5 you 
can see an example installation diagram. 

The various components in this diagram are:
 

a)  Return temperature monitor (pump unit).

 b) 

Expansion 

vessel.

 c) 

De-aerator.

 

d) Overpressure valve (3 bar)

 

e)  Thermal load valve.

 f) 

Water 

supply.

 

g) Circulation pump CH system

6. BURNING

● 

A Dik Geurts stove with CH heat exchanger by never be

 

fired without water!

● 

These appliances should first be filled with water and

 

de-aerated, and may only be taken into operation when the

 

functional installation has been fully completed.

See the User Manual, chapter 5, for lighting and burning the 
fire.

7. DELIVERY

You must explain to the user how to operate the fire. You 
should instruct her/him for instance on using the appliance for 
the first time, heating and maintenance.

● 

Instruct the user about the use of the fire.

● 

When the appliance is put into operation, point out that

● 

when the fire is heated up for the first time, volatile

 

components evaporate from paint, materials, etc.;

● 

the room should be well ventilated.

● 

Point out that the flue duct should be inspected and cleaned

 

at least once per year, by a specialist.

● 

Give the user manual and installation manual to the user (the

 

installation manual should be kept near the appliance).

● 

Point out to the user that the heat exchanger has to be

 

cleaned (see the user manual, chapter 2.1).

8. MAINTENANCE

There are a number of tips/instructions on the maintenance of 
the fire in Chapter 6, Maintenance, of the User Manual.  This 
also explains how a number of parts can be replaced.

9. MALFUNCTIONS

In chapter 7 of the User manual you will find an overview of 
malfunctions that might occur, the possible causes and the 
remedies.

Appendix 1 Parts supplied

In the following table you can find the parts that are supplied 
with the appliance.

Table 1: 

Caution

!

Caution

!

Part Quantity

Installation manual 

1

User manual 

1

Glove 1

Ash pan 

1

Glass cleaner spray bottle 

1

Spray can of heat-resistant paint 

1

Overpressure relief valve 

1

Thermal load valve 

1

Cleaning brush 

1

Summary of Contents for Dik Geurts

Page 1: ...05 11 01 2016 ...

Page 2: ......

Page 3: ...der toegelicht 3 3 5 1 Thermische veiligheidsklep 3 3 5 2 Het overdrukventiel 4 3 5 3 Ontluchting 4 UITPAKKEN 5 5 INSTALLATIE 5 5 1 Voorschriften 5 5 2 Rookgaskanaal 5 5 3 Voorzieningen plaatsing haard 5 5 4 Plaatsen haard 5 5 5 Aansluiten haard 5 6 STOKEN 6 7 OPLEVERING 6 8 ONDERHOUD 6 9 STORINGEN 6 Bijlage 1 Meegeleverde onderdelen 6 Bijlage 2 aansluitingen haard lijntekening 7 Bijlage 3 meegele...

Page 4: ...vaste platen Bovenin ligt een zogenaamde keerplaat om het rendement te verhogen De haard is uitgerust met een schuif voor de luchttoevoer een deel van de secundaire lucht wordt continu langs de bovenkant van de ruit geleid De haard is uitsluitend geschikt om gestookt te worden met hout of houtbriketten 2 EC CONFORMITEITSVERKLARING STORE De ondergetekende vertegenwoordiger van Fabrikant DRU Verwarm...

Page 5: ...e in de opstellingsruimte 3 4 Aanvullende veiligheidsvoorschriften voor haarden met cv wisselaar Bij de installatie van een Dik Geurts haard met cv wisselaar zijn de volgende zaken essentieel Installatie zonder de meegeleverde veiligheden is niet toegestaan Een haard van Dik Geurts wordt altijd geleverd met de onderstaande veiligheden Veiligheidswarmtewisselaar in het toestel geïnstalleerd Thermis...

Page 6: ... werking van het overdrukventiel rekening met het volgende sluit het overdrukventiel aan op de haard gebruik hiervoor een leiding met een minimale diameter van afsluiters en weerstanden in de leiding zijn niet toegestaan gebruik maximaal één bocht De leiding van het overdrukventiel naar de afvoer moet aan bepaalde eisen te voldoen Bij een leiding met een maximale lengte van 2 meter het maximale aa...

Page 7: ...pen tegen een wand van niet brandbaar materiaal plaats de haard en of de haardpijpen op minimaal 50 mm vanaf de wand plaats de haard en of de haardpijpen altijd op minimaal 700 mm afstand van brandbare objecten en of materialen plaats de haard op een brandwerende vloerplaat die volgens de geldende norm voor de haard uitsteekt als deze op een vloer van brandbaar materiaal komt te staan dek de haard...

Page 8: ...k genomen worden als de functionele installatie volledig afgerond is Zie de Gebruikershandleiding hoofdstuk 5 voor het aansteken en stoken van de haard 7 OPLEVERING U dient de gebruiker vertrouwd te maken met de haard U dient haar hem te instrueren over onder meer de ingebruikname het stoken en het onderhoud Instrueer de gebruiker over de haard Wijs er bij ingebruikname op dat bij de eerste keer s...

Page 9: ...Bijlage 2 Aansluiting haard Dik Geurts 7 N e d e r l a n d s 570 800 390 180 780 196 830 440 ...

Page 10: ...8 Bijlage 3 Meegeleverde beveiligingen 14 Figuur 1 Figuur 2 Figuur 3 Figuur 4 ...

Page 11: ...heid Luchtoevoer Ø cv aansluiting mm Pompunit verplicht Ø water aansluiting mm Regeltemperatuur pompunit C Verklaring van oplevering Firmastempel De gebruiker verklaart hiermee dat het toestel werkend is opgeleverd en hem haar is uitgelegd hoe het toestel te gebruiken en te onderhouden Datum en handtekening gebruiker Datum en handtekening installateur Dik Geurts The Netherlands Bijlage 4 Formulier...

Page 12: ...10 30 05 2012 Store 95 C 60 C B B A C D E F G Bijlage 5 Installatieschema ...

Page 13: ...afety valve 13 3 5 2 Overpressure relief valve 14 3 5 3 De aeration 14 REMOVING THE PACKAGING 15 5 INSTALLATION 15 5 1 Regulations 15 5 2 Flue duct 145 5 3 Provisions for placing the fire 15 5 4 Placing the fire 15 5 5 Connecting the fire 15 6 BURNING 16 7 DELIVERY 16 8 MAINTENANCE 16 9 MALFUNCTIONS 16 Appendix 1 Parts supplied 16 Appendix 2 connections fire line drawing 17 Appendix 3 safeguards s...

Page 14: ...o increase the efficiency The fire is equipped with a slide for air supply Part of the secondary air is continuously guided along the top of the glass pane The fire is only suitable to be filled with wood or wood briquettes 2 EC DECLARATION OF CONFORMITY STORE The undersigned representative of Manufacturer DRU Verwarming B V PO Box 1021 NL 6920 BA Duiven Ratio 8 NL 6921 RW Duiven Hereby declares t...

Page 15: ... stoves with CH heat exchanger When installing a Dik Geurts fire with CH heat exchanger the following is essential Installation without the supplied safety devices is not permitted A Dik Geurts fire is always supplied with the following safeguards Safety heat exchanger installed in the appliance Thermal safety valve with fluid filled detector and capillary tube Pressure relief valve 3 bar Check wh...

Page 16: ...ef valve take the following into account connect the overpressure relief valve to the fire for this use a pipe with a minimum diameter of valves and resistors are not allowed in the pipe use only one bend maximum The pipe from the overpressure relief valve to the discharge must comply with certain requirements In case of a pipe with a maximum length of 2 metres the maximum number of bends in this ...

Page 17: ...of non combustible material place the fire and or the flue pipes at least 50 mm away from the wall always place the fire and or the flue pipes at a minimum distance of 800 mm from combustible objects and or materials place the fire on a fire resistant floor plate extending in front of the fire in accordance with the applicable standard if it is placed on a floor made of combustible material do not...

Page 18: ...with water and de aerated and may only be taken into operation when the functional installation has been fully completed See the User Manual chapter 5 for lighting and burning the fire 7 DELIVERY You must explain to the user how to operate the fire You should instruct her him for instance on using the appliance for the first time heating and maintenance Instruct the user about the use of the fire ...

Page 19: ...E n g l i s h Dik Geurts 17 Appendix 2 Connection fire 570 800 390 180 780 196 830 440 ...

Page 20: ...18 Appendix 3 Safeguards supplied 14 Figuur 1 Figuur 2 Figuur 3 Figuur 4 Figure 1 Figure 2 Figure 3 Figure 4 ...

Page 21: ...ssibilities Air supply Ø CH connection mm Pump unit obligatory Ø water connection mm Control temperature pump unit C Declaration of delivery Firm stamp The user hereby declares that the appliance has been delivered in working order and that he she was explained how to use and maintain the appliance Date and signature user Date and signature installer Dik Geurts The Netherlands Appendix 4 Form for ...

Page 22: ...20 30 05 2012 Store 95 C 60 C B B A C D E F G Appendix 5 Installation overview ...

Page 23: ...fs de sécurité nécessaires 33 3 5 1 Valve de sécurité thermique 33 3 5 2 La valve de surpression 34 3 5 3 Purge 34 DÉBALLAGE 35 5 INSTALLATION 35 5 1 Prescriptions 35 5 2 Conduit de cheminée 35 5 3 Dispositifs de mise en place du poêle 35 5 4 Mise en place du poêle 35 5 5 Raccordement du poêle 35 6 COMBUSTION 36 7 LIVRAISON 36 8 ENTRETIEN 36 9 PANNES 36 Annexe 1 Pièces détachées fournies 36 Annexe...

Page 24: ...al La chambre de combustion est habillée de plaques de chamotte Sur le haut un déflecteur est installé pour augmenter le rendement Le poêle est équipé d une trappe pour l arrivée d air une partie de l air secondaire est conduit en continu le long du haut de la vitre Le poêle est uniquement conçu pour être alimenté au bois ou avec des briquettes de bois 2 DÉCLARATION DE CONFORMITÉ CE STORE Le souss...

Page 25: ...e par une entreprise de ramonage agréée n apportez personnellement aucune modification au poêle utilisez uniquement les pièces d origine pour remplacement veillez à ce que la ventilation soit suffisante dans la zone d installation 3 4 Mesures de précaution complémentaires pour les poêles avec échangeur de chauffage central Lors de l installation d un poêle Dik Geurts avec échangeur de chauffage ce...

Page 26: ...it toujours être installée Sans cette valve un fonctionnement sûr du système ne peut être garanti Pour un fonctionnement sûr et correct de la valve de surpression veuillez tenir compte des éléments suivants raccordez la valve de surpression sur le poêle pour ce faire utilisez un conduit d un diamètre minimal de le conduit ne peut présenter ni vanne ni résistance utilisez au maximum un coude Le con...

Page 27: ...z le poêle sur un sol présentant une portance suffisante placez le poêle et ou les tuyaux du poêle contre un mur composé de matériaux non inflammables placez le poêle et ou les tuyaux du poêle à 50 mm minimum du mur placez toujours le poêle et ou les tuyaux de celui ci à une distance minimale de 700 mm des objets et ou matériaux inflammables placez le poêle sur une plaque de sol résistant au feu q...

Page 28: ...limentation en eau g Pompe de circulation du système de chauffage central 6 COMBUSTION Un poêle Dik Geurts avec échangeur de chauffage central ne peut jamais chauffer sans eau Ces appareils doivent tout d abord être remplis d eau et purgés et ne peuvent être mis en service que lorsque l installation fonctionnelle est entièrement terminée Voir le Manuel de l utilisateur chapitre 5 pour l allumage e...

Page 29: ...Annexe 2 Raccordement poêle F r a n ç a i s Dik Geurts 27 570 800 390 180 780 196 830 440 ...

Page 30: ...Annexe 3 Protections fournies 28 14 Figuur 1 Figuur 2 Figuur 3 Figuur 4 Figure 1 Figure 2 Figure 3 Figure 4 ...

Page 31: ...Possibilité de nettoyage Arrivée d air Ø raccordementauchauffagecentral mm Unité de pompe obligatoire Øraccordement à l eau mm Températurederéglageunitédepompe C Déclaration de livraison Cachet de la société L utilisateur déclare par la présente que l appareil a été livré en parfait état de fonctionnement et qu il lui a été expliqué comment utiliser et entretenir l appareil Date et signature de l ...

Page 32: ...30 30 05 2012 Store 95 C 60 C B B A C D E F G Annexe 5 ...

Page 33: ...Dik Geurts 31 ...

Page 34: ......

Reviews: