10/25
Location
Signal level
Function
Note
Block
Num
M1
1
+
24 Vdc Inputs (Vio+)
Max level
17
IN +
Input P
2
-
0 Vdc Inputs (Vio-)
18
IN -
Input N
3
+
24 Vdc Inputs (Vio+)
Min level
19
IN +
Input P
4
-
0 Vdc Inputs (Vio-)
20
IN -
Input N
5
+
24 Vdc Inputs (Vio+)
Air pressure switch
Safety pressure switch
,
for example air-oil
systems
21
IN +
Input P
6
-
0 Vdc Input (Vio-)
22
IN -
Input N
7
+
24 Vdc Inputs (Vio+)
PULSE
Devices for counting
23
IN +
Input P
8
-
0 Vdc Inputs (Vio-)
24
IN -
Input N
9
+
24 Vdc Inputs (Vio+)
P1
First sensor input for system monitoring.
(Pressure injector, control loop for
progressive, suspend for timer…..)
25
IN +
Input P
10
-
0 Vdc Inputs (Vio-)
26
IN -
Input N
M1
11
+
24 Vdc Inputs (Vio+)
P2
Second sensor input for system monitoring.
(pressure 2 pressure switch dual line, Boost
for cycle SEP, ... )
27
IN +
Input P
12
-
0 Vdc Inputs (Vio-)
28
IN -
Input N
13
-
0 Vdc Inputs (Vio-)
Thermal protection
Input for motor thermal protection alarm
29
IN -
Input N
14
-
0 Vdc Inputs (Vio-)
Remote control
Enables remote control of the cycle
30
IN -
Input N
15
-
0 Vdc Inputs (Vio-)
Remote cycle start
If active the remote control input, activates
the cycle start
31
IN -
Input N
16
-
0 Vdc Inputs (Vio-)
Clear errors
Delete any errors
32
IN -
Input N
Location
Signal level
Function
Note
Block
Num
M2
1
Vac1
19 Vac
AC input
Possible inputs also with 24Vdc
2
Vac2
19 Vac
3
Earth
Earth
Earth connection
If you want to report back to the ground
power
c
onnect these terminals 2
4
Vint -
GND
internal logic
Power logic and relay
control
5
Vint +
24 V
internal logic
max 1,5 A
6
Vio -
0 Vdc Inputs
Supply of external
inputs
Max 1,2 A
7
Vio +
24 Vdc Inputs
8
Vio -
0 Vdc Inputs