drive.web automation
smarty
Comms Interfaces-CANopen, Modbus, EIP/PCCC
Warning!
Use of
smarty
comms interfaces may cause
motors and machinery to energize with high Voltages, or start,
or operate in unexpected, dangerous, or lethal ways.
For Modbus specs go to
smarty
Comms Server
dwOption-04 and -25
Note!
You cannot write or force parameters that are read-only or
have incoming
drive.web
connections.
Click the
Comms Server
icon in the
FBE
or
SFD
view.
dwOption-04
ModbusTCP/IP slave/server
Supported Modbus Function Codes; 1 thru 6, 15, and 16.
Supports up to
five simultaneous clients/masters
.
dwOption-25
EIP/PCCC Server
Supports PLC5 Typed-Write and Typed-Read commands.
See Appendix B of the
savvy
User Manual for information and
drive.web
parameter IDs mapping to PLC5.
Supports up to
two simultaneous clients
.
ModbusRTU
M
=Master-Client,
S
=Slave-Server,
X
=None. See pages 2 and 4.
Modbus Function Codes
FC
01
through
06
and
16
are
supported. Also special Yaskawa Holding Register.
Each server’s Modbus address must be unique on the network!
All devices on the network must have the same baud rate, up to
500.0kbps, and the same character framing.
dw259
Generic CANopen Master
Dedicated to a single server device at speeds up to 1Mbps.
1m max cable length.
Do not use termination resistors. These are built-in.
Use
CANopen Setup
function block to configure.
drive.web
Training Courses
Free
online interactive training seminars take about one hour.
Specialized online and factory training sessions are also
available.
To register email
or call.
smarty
HG504266Iss1.0
Page /12
12
drive.web
40 Log Canoe Circle, Stevensville, MD 21666 USA.
Ph. 410-604-3400, Fax 410-604-3500,